technical characteristics
vacon
10
24-hour s358 (0)40 837 1150 • Email: [email protected]
2
Digital pulse train output
Open collector output pulse train proportional to output frequency
Vmet analog output
0 to 10 Vdc (5 mAdc maximum)
Imet analog output
0–20 mAdc output into a 500
Ω
load (maximum)
DC holding / injection braking
At start, stop, by frequency with adjustable current level and time or contin-
uous DC injection by digital input
Current limit
Four quadrant adjustable from 5 to 150%
Speed ramps
Primary and alternate adjustable from 0.1 to 3200.0 seconds
Voltage boost
Fixed boost adjustable from 0 to 50% or auto boost
Voltage characteristic (V/Hz)
Linear, pump, fan or 2-piece linear
Timed overload
Adjustable inverse time trip (shear pin, 30 sec, 60 sec, 5 min), standard or in-
verterduty motors
Protective features
Overcurrent, overvoltage fault, ground fault, short circuit, dynamic brake
overload, drive temperature, power wiring fault, drive timed overload, input
voltage quality, overvoltage ridethrough
Program Sequence Logic Control-
ler (PSLC)
9-step PLC type functionality that can control speed, direction, and ramps
based on time, analog input, digital input, or pulse input
Serial communications
Modbus Standard: RTU
Summary of Contents for 50X
Page 1: ......
Page 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Page 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Page 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Page 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...