Parameters
vacon • 127
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.14.4
Group 3.13.4: FeedForward
Feedforward usually needs accurate process models, but in some simple cases a gain + offset type
of feedforward is enough. The feedforward part does not use any feedback measurements of the
actual controlled process value (water level in the example on page 170). VACON
®
feedforward
control uses other measurements which are indirectly affecting the controlled process value.
7.1.14.5
Group 3.13.5: Sleep Function
This function will put the drive into sleep mode if the frequency stays below the sleep limit for a lon-
ger time than that set with the Sleep Delay.
Table 108. Feedforward settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.4.1
1
9
1
1059 See P3.13.3.1.
P3.13.4.2
Gain
-1000
1000
%
100.0
1060 See P3.13.3.2
P3.13.4.3
FF 1 Source
0
25
0
1061 See P3.13.3.3
P3.13.4.4
FF 1 Minimum
-200.00
200.00
%
0.00
1062 See P3.13.3.4
P3.13.4.5
FF 1 Maximum
-200.00
200.00
%
100.00
1063 See P3.13.3.5
P3.13.4.6
FF 2 Source
0
25
0
1064 See P3.13.3.6
P3.13.4.7
FF 2 Minimum
-200.00
200.00
%
0.00
1065 See P3.13.3.7
P3.13.4.8
FF 2 Maximum
-200.00
200.00
%
100.00
1066 See P3.13.3.8
Table 109. Sleep function settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.5.1
0.00
320.00
Hz
0.00
1016
Drive goes to sleep mode when
the output frequency stays below
this limit for a time greater than
that defined by parameter
Sleep
delay
.
P3.13.5.2
0
3000
s
0
1017
The minimum amount of time
the frequency has to remain
below the Sleep level before the
drive is stopped.
P3.13.5.3
Varies
0.00
1018
Defines the level for the PID
feedback value wake-up super-
vision. Uses selected process
units.
P3.13.5.4
SP 1 WakeUpMode
0
1
0
1019
Select if wake up level should
work as an absolute level or as
an offset below the actual set-
point value.
0 = Absolute Level
1 = Relative Setpoint
P3.13.5.5
0.00
320.00
Hz
0.00
1075
Drive goes to sleep mode when
the output frequency stays below
this limit for a time greater than
that defined by parameter
Sleep
delay
.
P3.13.5.6
0
3000
s
0
1076
The minimum amount of time
the frequency has to remain
below the Sleep level before the
drive is stopped.