Parameters
vacon • 97
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P3.2.10
Rem to Loc Funct
0
2
2
181
Choose whether to copy the
Run state and Reference when
changing from Remote to Local
(keypad) control:
0 = Keep Run
1 = Keep Run & Reference
2 = Stop
P3.2.11
Start Analogue Signal
0
1
0
1810
0= AI1
1= AI2
P3.2.12
Start Analogue Level
0.00
100.00
%
10.00
1857
Start is set below this level
(unscaled signal). Start-stop
logic is reversed if > P3.2.13
P3.2.13
Stop Analogue Level
0.00
100.00
%
80.00
1856
Start is set above this level
(unscaled signal). Start-stop
logic is reversed if < P3.2.12
Table 64. Start/Stop Setup menu
Code
Parameter
Min
Max
Unit
Default
ID
Description