vacon • 108
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.6.5
Expander slots D and E digital outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selections as
in Standard RO1 (P3.5.3.2.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
7.1.6.6
Group 3.5.4: Analogue outputs
Group 3.5.4.1: Slot A Basic
7.1.6.7
Expander slots D to E analogue outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selections as
in Standard AO1 (P3.5.4.1.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
Table 81. Standard I/O board analogue output settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.4.1.1
0
19
2
10050
0=TEST 0% (Not used)
1=TEST 100%
2=Output freq (0 -fmax)
3=Freq reference (0-fmax)
4=Motor speed (0 - Motor nominal
speed)
5=Output current (0-InMotor)
6=Motor torque (0-TnMotor)
7=Motor power (0-PnMotor)
8=Motor voltage (0-UnMotor)
9=DC link voltage (0-1000 V)
10=PID1 output (0-100%)
11=Ext.PID output (0-100%)
12=ProcessDataIn1 (0-100%)
13=ProcessDataIn2 (0-100%)
14=ProcessDataIn3 (0-100%)
15=ProcessDataIn4 (0-100%)
16=ProcessDataIn5 (0-100%)
17=ProcessDataIn6 (0-100%)
18=ProcessDataIn7 (0-100%)
19=ProcessDataIn8 (0-100%)
P3.5.4.1.2
AO1 filter time
0.0
300.0
s
1.0
10051
Filtering time of analogue output sig-
nal. See P3.5.2.1.2
0 = No filtering
P3.5.4.1.3
AO1 minimum
0
1
0
10052
0 = 0 mA / 0 V
1 = 4 mA / 2 V
Signal type (current/voltage)
selected with dip switches.
Note the difference in analogue out-
put scaling in parameter P3.5.4.1.4.
See also parameter P3.5.2.1.3.
P3.5.4.1.4
Varies
Varies
Varies
0.0
10053
Min scale in process unit (depends
on selection of AO1 function).
P3.5.4.1.5
Varies
Varies
Varies
0.0
10054
Max scale in process unit (depends
on selection of AO1 function)