NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module
58878-EN-190215
+ h
D
- h
Fig. 17: Vessel height and socket correction value
D Vessel height
+h Positive socket correction value
-h Negative socket correction value
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of fault.
The default setting is output characteristics 4 … 20 mA, fault mode
< 3.6 mA.
In the menu item "
Current output Min./Max.
", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
The following circumstances cause interfering reflections and can
influence the measurement:
•
High mounting sockets
•
Vessel internals such as struts
Setup - Current output,
mode
Setup - Current output
Min./Max.
Setup - False signal sup-
pression