7 Diagnostics and servicing
58878-EN-190215
Measurement error during emptying
Fault description
Cause
Rectification
7. Measured value remains
unchanged in the close
range during emptying
Level
time
0
•
False signal larger than the level echo
•
Level echo too small
•
Eliminate false signals in the close
range
•
Remove contamination on the probe.
After having removed the source of the
false signals, the false signal suppres-
sion must be deleted.
•
Carry out a new false signal suppres-
sion
8. Measured value remains
reproducible in one position
during emptying
Level
time
0
•
Stored false signals in this position are
larger than the level echo
•
Delete false signal suppression
•
Carry out a new false signal suppres-
sion
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Setup
" must be carried out again or must
be checked for plausibility and completeness.
7.4 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
ics modules are adapted to the respective sensor and differ in signal
output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
•
In the factory
•
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
When loading on site, the order data must first be downloaded from
the Internet (see operating instructions "
Electronics module
").
Caution:
All application-specific settings must be entered again. That's why you
have to carry out a fresh setup after exchanging the electronics.
If you saved the parameter settings during the first setup of the sen
-
sor, you can transfer them to the replacement electronics module. A
fresh setup is then not necessary.
Reaction after fault recti-
fication
Summary of Contents for NivoGuide 8100
Page 72: ...72 NivoGuide 8100 Two wire 4 20 mA HART INDEX 58878 EN 190215 U Units 26 ...
Page 73: ...73 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Page 74: ...74 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Page 75: ...75 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...