NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module
58878-EN-190215
The sensor offers the HART modes "
Analogue current output
" and
"
Fix current (4 mA)
". In this menu item you determine the HART mode
and enter the address with Multidrop mode.
In the mode "
Fixed current output
" up to 63 sensors can be operated
on one two-wire cable (Multidrop operation). An address between 0
and 63 must be assigned to each sensor.
If you select the function "
Analogue current output
" and also enter
an address number, you can output a 4 … 20 mA signal in Multidrop
mode.
In the mode "
Fixed current (4 mA)
" a fixed 4 mA signal is output inde
-
pendently of the actual level.
The default setting is "
Analogue current output
" and the address 00.
In this menu item you gain access to the protected area where
you can enter special parameters. In exceptional cases, individual
parameters can be modified in order to adapt the sensor to special
requirements.
Change the settings of the special parameters only after having con-
tacted our service staff.
In this menu, you read out the instrument name and the instrument
serial number.
In this menu item, the hardware and software version of the sensor is
displayed.
In this menu item, the date of factory calibration of the sensor as well
as the date of the last change of sensor parameters are displayed via
the display and adjustment module.
Additional settings -
HART mode
Additional settings - Spe-
cial parameters
Info - Instrument name
Info - Instrument version
Info - Factory calibration
date
Summary of Contents for NivoGuide 8100
Page 72: ...72 NivoGuide 8100 Two wire 4 20 mA HART INDEX 58878 EN 190215 U Units 26 ...
Page 73: ...73 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Page 74: ...74 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Page 75: ...75 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...