ÜKY/Duopel Boilers User Manual
FUEL FEEDING – STANDBY ADJUSTMENT
ÜNMAK DUOPEL serisi kazanların kontrol panelinden ayarlanabilen, otomatik beslemeli çalıştırma
besleme ve bekleme ayarları için tablo tablosu kullanılabilir.
Do not open the boiler covers and the hopper cover during power cuts, do not add
water to the boiler.
The values given according to the capacities in the table will vary according to the
chimney draft and the thermal comfort demand of the space.
In power cuts; close the flue flap, if any. If the pump bypass line is available, activate
the line. When the electricity comes, do not forget to return your settings.
Features of water suitable for filling in boiler installation
Parameter
Unit
Boiler feeding water
Boiler adding water
Appearance
-
Clean, clear, free from solids and stable foam
Conductivity at 25
o
C
S/cm
<1500
pH at 25
o
C
-
>0,7
9,0 dan 11,5
Total hardness (Ca+Mg)
mmol/l
<0,05
Ferrite concentration
mg/l
<0,2
Compound alkali value
mmol/l
-
<5
Diesel / oil concentration
mg/l
<1
-