Engineering Guide
Space Saver
19
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW8G* Valve Size: 1"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
22.5
15.35
3520
95,390
75,290
90,850
73,310
86,750
71,840
83,570
70,080
3200
93,890
73,100
89,420
71,180
85,390
69,750
82,260
68,040
2880
92,570
70,900
88,160
69,040
84,190
67,650
81,100
65,990
15
7
3520
85,620
67,580
81,550
65,810
77,870
64,490
75,020
62,910
3200
84,280
65,620
80,270
63,900
76,650
62,620
73,840
61,080
2880
83,100
63,650
79,140
61,980
75,570
60,740
72,800
59,240
7.5
1.84
3520
65,730
51,880
62,600
50,520
59,780
49,500
57,590
48,290
3200
64,700
50,370
61,620
49,050
58,840
48,060
56,690
46,890
2880
63,790
48,850
60,750
47,570
58,010
46,610
55,890
45,480
45
22.5
15.35
3520
105,970
83,650
100,930
81,460
96,380
79,820
92,860
77,870
3200
104,310
81,220
99,350
79,090
94,870
77,500
91,400
75,610
2880
102,840
78,780
97,950
76,710
93,540
75,170
90,120
73, 340
15
7
3520
95,130
75,090
90,610
73,130
86,530
71,660
83,360
69,900
3200
93,640
72,910
89,190
71,000
85,170
69,580
82,050
67,870
2880
92,320
70,720
87,940
68,810
83,970
67,490
80,900
65,830
7.5
1.84
3520
73,040
57,640
69,560
56,130
66,420
55,010
63,990
53,660
3200
71,890
55,970
68,470
54,500
65,380
53,410
62,990
52,100
2880
70,880
54,290
67,510
52,860
64,460
51,800
62,100
50,530
42
22.5
15.35
3520
116,570
92,020
111,020
89,610
106,020
87,810
102,130
85,660
3200
114,740
89,340
109,280
87,000
104,360
85,260
100,530
83,170
2880
113,130
86,650
107,750
84,390
102,890
82,700
99,120
80,670
15
7
3520
104,640
82,600
99,660
80,440
95,170
78,820
91,690
76,890
3200
103,000
80,200
98,100
78,100
93,680
76,530
90,250
74,660
2880
101,550
77,790
96,720
75,150
92,360
14,230
88,980
72,420
7.5
1.84
3520
80,330
63,400
76,510
61,740
73,070
60,510
70,380
59,020
3200
79,070
61,560
75,310
59,950
71,920
58,750
69,280
57,310
2880
77,960
59,710
74,250
58,150
70,910
56,980
68,310
55,590
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.