Engineering Guide
Space Saver
26
Subject to change without notice.
20.3-TD (1018)
Selection Procedure
Design Parameters
Model: VSW5G3AS
Entering DB
76
WB
64
Entering Water Temp�:
80
GPM
15
CFM
2200
Cooling:
Locate data for specific model at rated conditions
Example: 2000 CFM, 80 / 67 and
85 EWT and 15 GPM�
Total 66,900
Sensible 48,000
Cooling Capacity Correction Factors at Design Conditions
Total
0�97
Sensible 0�962
CFM
1�02
EWT @ GPM
1�014
Estimated Design Performance
Total
66,900
x Corr. For WB
X 0.97
x Corr. For CFM
X 1.02
x Corr. For EWT / GPM
X 1.014
67,117
Sensible
48,000
x Corr. For WB / DB
X 0.962
x Corr. For CFM
X 1.02
x Corr. For EWT / GPM
X 1.014
47,758