Engineering Guide
Space Saver
17
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW6G* Valve Size: 1"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
15
10.97
2640
69,510
54,050
66,210
52,640
63,220
51,580
60,900
50,320
2400
68,420
52,480
65,170
51,110
62,230
50,080
59,950
48,860
2160
67,460
50,900
64,250
49,570
61,350
48,570
59,110
47,390
10
5
2640
62,400
48,520
59,430
47,250
56,750
46,300
54,680
45,170
2400
61,420
47,110
58,500
45,880
55,860
44,960
53,820
43,860
2160
60,560
45,690
57,680
44,500
55,070
43,610
53,060
42,540
5
1.32
2640
47,900
37,250
45,620
36,270
43,560
35,540
41,970
34,680
2400
47,150
36,170
44,910
35,220
42,880
34,510
41,310
33,670
2160
46,480
35,080
44,280
34,160
42,270
33,470
40,730
32,650
45
15
10.97
2640
77,240
60,060
73,560
58,490
70,250
57,310
67,670
55,910
2400
76,030
58,320
72,410
56,190
69,150
55,650
66,610
54,290
2160
74,960
56,570
71,390
55,080
68,180
53,980
65,670
52,660
10
5
2640
69,340
53,920
66,040
52,500
63,060
51,450
60,750
50,190
2400
68,250
52,350
65,000
50,980
62,070
49,960
59,800
48,730
2160
67,290
50,770
64,090
49,450
61,200
48,460
58,960
47,260
5
1.32
2640
53,220
41,380
50,690
40,300
48,410
39,490
46,630
38,520
2400
52,390
40,180
49,900
39,130
47,650
38,340
45,900
37,400
2160.
51,650
38,970
49,200
37,950
46,980
37,180
45,250
36,270
42
15
10.97
2640
84,960
66,060
80,920
64,330
77,270
63,040
74,440
61,500
2400
83,630
64,140
79,650
62,460
76,060
61,210
73,270
59,710
2160
82,450
62,210
78,530
60,580
74,990
59,370
72,240
57,910
10
5
2640
76,270
59,300
72,640
57,750
69,370
56,580
66,830
55,200
2400
75,070
57,580
71,500
56,070
68,280
54,940
65,780
53,600
2160
74,010
55,850
70,490
54,380
67,320
53,290
64,850
51,990
5
1.32
2640
58,550
45,520
55,760
44,330
53,240
43,430
51,290
42,370
2400
57,630
44,200
54,890
43,040
52,410
42,170
50,490
41,140
2160
56,820
42,870
54,120
41,740
51,670
40,900
49,780
39,900
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.