Chilled Water Coil Performance
VSCW4G* Valve Size: 3/4"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
10.5
15.35
1760
46,300
37,010
44,100
36,050
42,110
35,320
40,560
34,460
1600
45,580
35,940
43,410
35,000
41,450
34,300
39,930
33,460
1440
44,940
34,860
42,800
33,950
40,860
33,270
39,370
32,450
7
7
1760
41,560
33,220
39,590
32,360
37,800
31,710
36,420
30,930
1600
40,910
32,260
38,970
31,420
37,210
30,790
35,850
30,030
1440
40,330
31,290
38,420
30,470
36,680
29,860
35,340
29,120
3.5
1.84
1760
31,900
25,510
30,380
24,840
29,010
24,330
27,950
23,740
1600
31,400
24,770
29,910
24,120
28,560
23,630
27,510
23,050
1440
30,960
24,020
29,490
23,390
28,160
22,920
27,120
22,350
45
10.5
15.35
1760
51,450
41,140
49,000
40,060
46,780
39,260
45,070
38,290
1600
50,640
39,950
48,230
38,900
46,050
38,120
44,370
37,180
1440
49,930
38,750
47,550
37,730
45,400
36,970
43,740
36,060
7
7
1760
46,180
36,930
43,990
35,960
42,010
35,240
40,460
34,380
1600
45,460
35,860
43,300
34,920
41,350
34,220
39,830
33,380
1440
44,820
34,780
42,690
33,870
40,770
33,190
39,270
32,370
3.5
1.84
1760
35,450
28,340
33,770
27,600
32,240
27,040
31,060
26,380
1600
34,900
27,520
33,240
26,800
31,740
26,260
30,580
25,620
1440
34,410
26,690
32,770
25,990
31,290
25,470
30,150
24,850
42
10.5
15.35
1760
56,600
45,240
53,900
44,060
51,480
43,170
49,590
42,110
1600
55,710
43,930
53,060
42,780
50,670
41,920
48,810
40,890
1440
54,930
42,610
52,310
41,490
49,960
40,660
48,120
39,660
7
7
1760
50,810
40,620
48,390
39,560
46,200
38,760
44,510
37,810
1600
50,010
39,440
47,630
38,410
45,480
37,640
43,810
36,710
1440
49,300
38,250
46,960
37,250
44,840
36,510
43,190
35,600
3.5
1.84
1760
38,990
31,170
37,140
30,360
35,460
29,750
34,160
29,020
1600
38,380
30,270
36,560
29,480
34,910
28,890
33,630
28,180
1440
37,840
29,360
36,040
28,590
34,420
28,020
33,150
27,330
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.