Engineering Guide
Space Saver
21
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW12G* Valve Size: 1-1/4"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
30
13.13
5280
146,910
113,660
139,920
110,670
133,620
108,450
128,720
105,800
4800
144,600
110,350
137,720
107,450
131,520
105,300
126,700
102,720
4320
142,570
107,030
135,790
104,220
129,670
102,140
124,920
99,630
20
6
5280
131,880
102,030
125,600
99,350
119,940
97,360
115,540
94,970
4800
129,810
99,060
123,630
96,460
118,060
94,530
113,730
92,210
4320
127,990
96,080
121,890
93,560
116,400
91,690
112,130
89,440
10
1.58
5280
101,240
78,320
96,420
76,270
92,080
74,730
88,700
72,910
4800
99,650
76,040
94,910
74,050
90,630
72,560
87,310
70,790
4320
98,250
73,750
93,580
71,820
89,360
70,380
86,080
68,660
45
30
13.13
5280
163,250
126,290
155,470
122,980
148,470
120,520
143,030
117,560
4800
160,680
122,620
153,030
119,400
146,140
117,010
140,780
114,140
4320
158,430
118,940
150,880
115,810
144,090
113,490
138,800
110,710
20
6
5280
146,540
113,370
139,570
110,390
133,280
108,180
128,400
105,530
4800
144,240
110,070
137,375
107,180
131,190
105,030
126,380
102,460
4320
142,220
106,760
135,450
103,960
129,350
101,870
124,610
99,380
10
1.58
5280
112,500
87,030
107,140
84,740
102,320
83,040
98,570
81,000
4800
110,730
84,500
105,460
82,280
100,710
80,630
97,020
78,650
4320
109,170
81,960
103,980
79,810
99,300
78,210
95,660
76,290
42
30
13.13
5280
179,570
138,910
171,030
135,260
163,330
132,560
157,340
129,310
4800
176,750
134,870
168,340
131,330
160,760
128,700
154,870
125,550
4320
174,270
130,820
165,980
127,390
158,500
124,830
152,700
121,780
20
6
5280
161,190
124,700
153,520
121,420
146,610
118,990
141,240
116,080
4800
158,660
121,070
151,110
117,890
144,310
115,530
139,020
112,700
4320
156,430
117,430
148,990
114,350
142,280
112,060
137,070
109,310
10
1.58
5280
123,740
95,720
117,850
93,210
112,550
91,350
108,420
89,100
4800
121,800
92,940
116,000
90,500
110,780
88,690
106,720
86,510
4320
120,090
90,150
114,370
87,780
109,220
86,020
105,220
83,910
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.