Engineering Guide
Space Saver
22
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW15G* Valve Size: 1-1/4"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
37.5
19.7
6600
173,920
136,150
165,640
132,580
158,190
129,920
152,380
126,740
6000
171,190
132,190
163,040
128,720
155,700
126,140
149,990
123,050
5400
168,790
128,220
160,750
124,850
153,520
122,350
147,890
119,350
25
9
6600
156,120
122,210
148,700
119,010
142,000
116,620
136,800
113,770
6000
153,670
118,660
146,360
115,550
139,770
113,230
134,650
110,460
5400
151,510
115,100
144,310
112,080
137,810
109,830
132,760
107,140
12.5
2.37
6600
119,850
93,820
114,150
91,360
109,010
89,520
105,020
87,330
6000
117,970
91,090
112,360
88,700
107,300
86,920
103,370
84,190
5400
116,310
88,350
110,780
86,030
105,790
84,310
101,920
82,240
45
37.5
19.7
6600
193,260
151,280
184,060
147,310
175,770
144,350
169,330
140,820
6000
190,220
146,880
181,170
143,020
173,010
140,150
166,670
136,720
5400
187,550
142,470
178,630
138,720
170,580
135,940
164,330
132,610
25
9
6600
173,490
135,800
165,230
132,240
157,790
129,590
152,000
126,420
6000
170,760
131,850
162,630
128,390
155,310
125,820
149,610
122,740
5400
168,360
127,890
160,350
124,530
153,130
122,040
147,510
119,050
12.5
2.37
6600
133,180
104,250
126,840
101,510
121,130
99,470
116,690
97,040
6000
131,090
101,220
124,850
98,560
119,230
96,580
114,860
94,220
5400
129,250
98,180
123,100
95,600
117,560
93,680
113,250
91,390
42
37.5
19.7
6600
212,580
166,400
202,460
162,030
193,350
158,790
186,260
154,900
6000
209, 240
161,560
199,280
157,320
190,310
154,170
183,330
150,390
5400
206,310
156,710
196,490
152,600
187,640
149,540
180,760
145,870
25
9
6600
190,830
149,380
181,750
145,450
173,560
142,540
167,200
139,050
6000
187,830
145,030
178,890
141,220
170,830
138,390
164,570
135,000
5400
185,200
140,670
176,380
136,980
168,430
134,230
162,260
130,950
12.5
2.37
6600
146,490
114,660
139,520
111,660
133,240
109,420
128,360
106,130
6000
144,190
111,330
137,330
108,410
131,150
106,240
126,340
103,630
5400
142,170
107,990
135,400
105,150
129,310
103,050
124,570
100,520
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.