Engineering Guide
VertiCool ™ Classic
15
Subject to change without notice.
20.10-TD (0816)
Notes:
(a) Electric heaters nominally rated at 220 or 277 volts� Amps listed at 230 or 460 volts�
(b) Electric heaters listed being used for heat�
(c) Use Copper Conductors Only�
(d) Values listed are typical and may vary dependent upon components utilized�
(e)
All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Electrical Data Air-Cooled
(c) (d) (e)
Tons
Voltage
Compressor
RLA
Evaporator Motor
Condenser Motor
Electrical Heat (a) (b)
MCA
MOP
HP
FLA
HP
FLA
Nom. KW
Amps
VA3G*ASTA
208/230-
3-60
13�5
460-3-60
6
VA4G*ASTA
208/230-
3-60
14�5
460-3-60
6�3
VA5G*ASTA
208/230-
3-60
19�2
460-3-60
8�7
VA8G*ATA
208/230-
3-60
14�5 ea�
1�5
4�8
2
6�2
- - -
- - -
43�6
55
2
6�2
3
9�2
- - -
- - -
48�0
60
1�5
4�8
2
6�2
10
27�4
43�6
55
2
6�2
3
9�2
25
68�6
93�5
95
460-3-60
6�3 ea�
1�5
2�4
2
3�1
- - -
- - -
19�7
25
2
3�1
3
4�3
- - -
- - -
21�6
25
1�5
2�4
2
3�1
10
11�5
19�7
25
2
3�1
3
4�3
25
28�8
39�9
40
VA10G*ATA
208/230-
3-60
19�2 ea�
1�5
4�8
3
9�2
- - -
- - -
57�2
75
2
6�2
5
13�6
- - -
- - -
63�0
80
1�5
4�8
3
9�2
15
41�2
57�5
75
2
6�2
5
13�6
30
82�3
110�6
115
460-3-60
8�7 ea�
1�5
2�4
3
4�3
- - -
- - -
26�3
30
2
3�1
5
6�3
- - -
- - -
29�0
35
1�5
2�4
3
4�3
15
17�3
26�3
30
2
3�1
5
6�3
30
34�6
47�1
50