Engineering Guide
VertiCool ™ Classic
5
Subject to change without notice.
20.10-TD (0816)
Physical Data
Notes
:
(a) Requires optional motor / drive upgrade�
(b) Net operating weight is for basic unit only� Options will add weight�
(c) Refrigerant circuit components will impact unit performance�
(d) 575 volt available� Contact factory�
(e) Contact factory for geothermal applications�
(f)
R-410a Refrigerant charge is base unit configuration. Addition of some options may alter refrigerant amount.
(g) Units always shipped split�
(h) Pulley & Belt upgrade only�
Tons
12
15
20
25
30 (g)
Evaporator Supply Air
CFM
4800
6000
8000
9770
12000
Std� ESP
0�25”
1�0”
Max� ESP (a)
1�0”
2�0”
Evaporator Blower
Size
15-9
15 - 15
Qty
2
Evaporator Motors
Std� HP
3
10
Opt� HP
5
15
Evaporator Coil
Rows
4
Face Area
13�33
17�8
22�6
FPI
10
12
Filter
Type
Pleated Throwaway
Qty
4
8
4 / 4
Dimensions
20 x 24 x 2
16 x 20 x 2
20 x 20 x 2 / 20 x
25 x 2
Efficiency
MERV 8
Compressor
Type
Scroll
Qty
2
Condenser Air
CFM
7200
9000
12000
15000
16000
Std� ESP
0�25”
1�0”
Max� ESP (a)
1�0”
2�0”
Condenser Blower
Size
15 - 9
18 - 18
Qty
3
2
Condenser Motors
Std� HP
5
10
15
Opt� HP
5 (d)
7�5
7�5
15
15 (h)
Condenser Coil
Rows
4
6
Face Area
20
22�7
FPI
12
Water Cooled Cond. (e)
Type
Co-axial
Qty
2
Weight (Net Operating)
(b)
Air-Cooled
1895
1895
1945
1980
3400
Water-Cooled
1435
1435
1485
1520
2700
Water Source HP
1495
1495
1545
1580
3000
Available Voltages (d)
208/230-3-60
•
•
•
•
•
460-3-60
•
•
•
•
•
Summary of Contents for VertiCool Classic Series