Notes:
(a) Capacities are gross values, not adjusted for motor heat�
(b)
Pressure drop is for heat exchanger only and does not include piping, valves, fittings, etc.
(c) Some refrigerant circuit components may impact on unit capacities�
(d) Values at 70° F Entering Water Temperature�
(e) Contact factory for geothermal applications�
Water Source Heat Pump Performance Data
(a) (c) (d) (e)
Tons
GPM
CFM
Entering Air Temp. (°F)
Heating Capacity
DB
VW3G*ATA
9
1200
70
50100
60
51100
VW4G*ATA
12
1600
70
62500
60
64000
VW5G*ATA
15
2000
70
78400
60
80100
VW8G*ATA
24
3200
70
94500
60
96500
VW10G*ATA
30
4000
70
116600
60
119100
VW12G*ATA
36
4800
70
136500
60
139400
VW15G*ATA
45
6000
70
178500
60
182300
VW20G*ATA
60
8000
70
225800
60
230700
VW25G*ATA
75
10000
70
275800
60
281800
VW30G*ATA
90
12000
70
358400
60
366200