Engineering Guide
VertiCool ™ Classic
25
Subject to change without notice.
20.10-TD (0816)
Application Data
Miscellaneous Technical Data
Voltage
208 / 230
460
575
Variation
187 / 253
414 / 504
518 / 632
Cooling (Air Entering Evaporator)
DB (min�/max�)
65 / 110
WB (min�/max)
57 / 72
Note: Not all combinations may be valid
Note: Not all combinations may be valid
Water-Cooled
GPM / Ton (min�/max�)
2�5 / 3�5
Leaving Water Temp (min�/max)
60 / 115
Water-Cooled Units
Female Pipe Threads (FPT)
Water Connection Sizes
Tons
Size
8
1”
10 - 12
1-1/4”
15
1-1/2”
20 - 30
2-1/2”
Condensate Drain Pipes:
3/4” IPS
Notes:
Reference United CoolAir’s Louver and Ducting Guidelines TechTip for proper selection
andapplication of wall louvers� You can view it on our website at www�unitedcoolair�com/
tips or click here if you are reading this document electronically�