(a) Electric heaters nominally rated at 220, 460 or 575 volts� Amps listed at 220, 460 or 575 volts�
(b) Electric heaters listed being used for heat�
(c) Use Copper Conductors Only�
(d) Values listed are typical and may vary dependent upon components utilized�
(e)
All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Electrical Data Water-Cooled
(c) (d) (e)
Tons
Voltage
Compressor
RLA
Evaporator Motor
Electrical Heat (a) (b)
MCA
MOP
HP
FLA
Nom. KW
Amps
3
4
5
8
208/230-3-60
14�5 ea�
1�5
4�8
- - -
- - -
37�4
50
2
6�2
- - -
- - -
38�8
50
1�5
4�8
10
27�4
40�3
50
2
6�2
25
68�6
93�5
95
460-3-60
6�3 ea�
1�5
2�4
- - -
- - -
16�6
20
2
3�1
- - -
- - -
17�3
20
1�5
2�4
10
11�5
17�4
20
2
3�1
25
28�8
39�9
40
10
208/230-3-60
19�2 ea�
1�5
4�8
- - -
- - -
48�0
65
2
6�2
- - -
- - -
49�4
65
1�5
4�8
15
41�2
57�5
65
2
6�2
30
82�3
110�6
115
460-3-60
8�7 ea�
1�5
2�4
- - -
- - -
22�0
30
2
3�1
- - -
- - -
22�7
30
1�5
2�4
15
17�3
24�6
30
2
3�1
30
34�6
47�1
50