Engineering Guide
VertiCool ™ Classic
11
Subject to change without notice.
20.10-TD (0816)
Electrical Data
The following sections provides the formulas and the data to calculate the Minimum Circuit Ampacity (MCA) and the
Maximum Fuse Size (MOP) for your specific unit configuration.
There are a variety of unit configurations. Please make sure to use the correct formulas per your configuration.
It must be noted that the formulas refer to the largest motor amps� This typically is the compressor (RLA), but it can also
be one of the blower motors (FLA)�
The data provided will cover the majority of available unit configurations. However, it should be noted that additional
combinations may be available and the factory can be contacted for this data�
Examples have also been provided for each configuration.
RLA
= Compressor Rated Load Amps
FLA
= Full Load Amps (Used for Blower Motors and Electric Heaters)
MCA
= Minimum Circuit Ampacity (Calculated value)
MOP
= Maximum Fuse Size (Calculated value)
Cooling Only:
Package Unit
NOTE
: Largest motor amps may not always be the compressor�
MCA
= (1�25 x largest motor amps) + the sum of the remaining motors
MOP
= (2�25 x largest motor amps) + the sum of remaining motors
Condensing Section w/ Compressor(s)
NOTE
: Largest motor amps may not always be the compressor�
MCA
= (1�25 x largest motor amps) + the sum of the remaining motors
MOP
= (2�25 x largest motor amps) + the sum of remaining motors
Evaporator Only Section
MCA
= (1�25 x Evap� Blower Motor Amps)
MOP
= (2�25 x Evap� Blower Motor Amps)
Condenser Only Section w/o Compressor(s)
MCA
= (1�25 x Cond� Blower Motor Amps)
MOP
= (2�25 x Cond� Blower Motor Amps)
Evaporator Section w/ Compressor(s)
NOTE
: Largest motor amps may not always be the compressor�
MCA
= (1�25 x largest motor amps) + the sum of the remaining motors
MOP
= (2�25 x largest motor amps) + the sum of remaining motors