AC-2100 User Guide
48
value of Door_Monitor_0 port is changed. In such a case, the pre-set pop-up
message saved in the server is displayed.
The sensor monitor1 port uses the same port as the door monitor pin. Therefore,
if Menu
3.Option
3.Set Doorlock
<Door Monitor> is set to ‘1’ or ‘2’, this port
is set to ‘0.None’ under any conditions.
If <Sensor Monitor1> is set to ‘1’ or ‘2’, the menu to select port state
transmission option is displayed. Port state information can be sent to the server
only once when the port state becomes “On” or whenever the port state is
changed.
<Send On/Off?>
1.Yes
2.No
[ESC][
↑
][
↓
][ENT]
If it is set to default setting ‘2.No’, port state
information is sent only when the port state
becomes “On”.
If it is set to ‘1.Yes’, port state information is
sent to the server whenever the port state is
changed.
Press [ENT] button to continue setting.
3.7.3.2. Sensor Monitor 2 Input Port Setting
Set up when Door_Monitor_1 port is connected to a sensor of fire detection or
emergency detection.
<Sensor Monitor1>
0.None
1.Normal Open
2.Normal Close
3.Fire NO
[ESC][
↑
][
↓
][ENT]
Default ‘0’: It doesn’t check port status.
- ‘0.
None
’: If nothing is connected
- ‘1. Normal Open’ or ‘2. Normal Close’: If sensor defined in sever is connected
- ‘3.Fire NO’ or ‘4.Fire NC’: If fire detection sensor is connected
- ‘5.Panic NO’ or ‘6.Panic NC’: If panic situation detection sensor is connected
- ‘7.Emergency NO’ or ‘8.Emergency NC’: If emergency detection sensor
is connected
Set up NO/NC as per status of input pin when detecting.
If fire detection (3 or 4) is set, connected gate will be open and the alarm will
go off while detecting fire sensor.