7: Options
7-4
UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
7.4.1 Remote Singalling Panel connections
• Provide a 0.75 mm2 minimum, shielded cable (max. 100 metre)
• Do not connect the shielding.
• Both ends of the cable are to be terminated in a terminal block connection at the Remote Status Panel
and at the UPS in accordance with Figure 7.3.
Figure 7.4 Connection of Remote Status Panel (RSP)
X1/1
X1/9
X1/10
X1/18
X1/19
3
4
5
2
6
+12V
Battery Low
Load on Mains/Inv
Mains Failure
Ground
UPS X1
Interface Block
Remote Signalling Panel
Terminal Block
Cabinet B/C
Cabinet A