UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
3-17
3: Installation
3.6.2 X1-21 Dry Port (volt-free contacts)
All the Input and Output interfaces to X1 are connected to Phoenix terminals (cable 0.5 mm2). All voltage free
contacts are rated 60 VAC max. and 500 mA max.
These output can be used to control an automatic and orderly shutdown of servers, AS400 or automated
building facilities.
Figure 3.12 Dry Port (X1-21)connections
Term.
Contact
Signal
Function
1
NO
ALARM
MAINS FAILURE
Mains Failure
Mains Present
2
COM
3
NC
4
NO
ALARM
COMMON ALARM
Common Alarm
No Alarm Condition
5
COM
6
NC
7
NO
STATUS
LOAD ON INVERTER
Load on Inverter
Load on Bypass
8
COM
9
NC
10
NO
ALARM
BATTERY LOW
Battery Low
Battery OK
11
COM
12
NC
13
NO
STATUS
LOAD ON MAINS
Load on Bypass
Load on Inverter
14
COM
15
NC
16
–
–
Control
Input
ON GENERATOR
Terminals are linked when the standby
generator is on-line.
17
18
+12V (100mA)
0V
Output
supply
.
19
20
–
–
Control
Input
REMOTE SHUTDOWN
NC contact wired to a remote emergency
stop circuit. Linked out when not used.
21
Summary of Contents for PowerWave 3000T
Page 1: ...Pioneering solutions for total power protection PowerWave PW 3000 T User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 30: ...3 Installation 3 18 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 44: ...4 Operation 4 14 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 56: ...7 Options 7 8 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...