4: Operation
4-10
UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
Closing the Maintenance Bypass switch:
5.
Close the Maintenance Bypass switch IA1.
6.
Confirm that:
a)
The
INVERTER
LED has turned to red.
b)
The
BYPASS
LED is green.
c)
The LCD displays
MANUAL BYP IS CLOSED
.
Powering down the UPS module:
When the load is connected to the Maintenance Bypass supply, as described above, the UPS module can be
powered down (for example, if required for maintenance/testing) using the following procedure:
7.
On the UPS control panel simultaneously press both
ON/OFF
buttons.
a)
The LCD panel will indicate:
LOAD OFF, SUPPLY FAILURE
.
8.
Open the battery fuse/isolator F1.
Note:
If using external batteries open the battery fuses/isolator on the associated battery cabinet/rack.
9.
On the UPS module open the module’s Output Isolator (IA2).
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Green
BY PASS
Green
INVERTER
OFF
BATTERY
Green
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Green
BY PASS
Green
INVERTER
RED
BATTERY
Green
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Off
BY PASS
Off
INVERTER
Off
BATTERY
Green Flashing
Summary of Contents for PowerWave 3000T
Page 1: ...Pioneering solutions for total power protection PowerWave PW 3000 T User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 30: ...3 Installation 3 18 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 44: ...4 Operation 4 14 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 56: ...7 Options 7 8 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...