4: Operation
4-8
UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
Maintenance Bypass switch (IA1)
The Maintenance Bypass mode is effected by means of the IA1 BYPASS SWITCH on the front/rear of the
UPS:
Switch IA1
Effect
ON
Maintenance Bypass-Switch Closed (Load on bypass mains)
LCD-indication:
MAINTENANCE BYP CLOSED
LED Indicators will indicate as shown in the table below
OFF
Bypass-Switch Open – Normal operating condition (Load on inverter)
LCD-indication
MAINTENANCE BYP OPEN
LED Indicators will indicate as shown in the table below.
LED Indicator
ON
OFF
LINE 1
Green
Green
LINE 2
Green
Green
BYPASS
Green
OFF
INVERTER
RED
ON
BATTERY
Green
Green
CAUTION: If the UPS is operating in the Maintenance Bypass mode the load will not be
protected in the event of a mains failure. It is therefore strongly recommended to switch over to
the on-line mode or bypass mode as soon as possible.