8: Specifications
8-4
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
8.8
Battery Operation (
MINIpowerPLUS 10000)
8.9
Bypass
8.10 Reference Standards
UPS Model Range
MINIpowerPLUS 10000
5000/2
6250/2
7500/2
8750/2
10000/2
Percentage load
50
80
100
50
80
100
50
80
100
50
80
100
50
80
100
*
Standard Autonomy
20
11
8
20
11
8
20
11
8
20
11
8
20
11
8
Recharge time to
90% charge
5 - 6 hours according to level of discharge
Specifications and
quantity of batteries
3 pcs 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each power module
Reserve signals
32.2 V to 36V, programmable
Minimum voltage for
battery operation
during discharge
27V to 31.5V with automatic selection depending on applied load, or as programmed by operator.
*Approximate autonomy in minutes with fully charged batteries
UPS Model Range
MINIpowerPLUS 5000
MINIpowerPLUS 10000
1250
2500
3750
5000
5000/2
6250/2
7500/2
8750/2
10000/2
Type
Static and electromechanical
Switchover time
Zero
UPS Model Range
MINIpowerPLUS 5000
MINIpowerPLUS 10000
1250
2500
3750
5000
5000/2
6250/2
7500/2
8750/2
10000/2
Safety
Conforms to standard EN 62040-1-1
Electromagnetic
compatibility
Immunity: Conforms to standard EN 50091-2 (class A)
Emissions: Conforms to standard EN 50091-2 (class B)
Typical Performance
Conforms to standard EN 62040-3
Summary of Contents for Minipower Plus Rack
Page 1: ...Pioneering solutions for total power protection MINIpower PLUS User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 26: ...3 Installation 3 12 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 40: ...5 Maintenance 5 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 42: ...6 Troubleshooting 6 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...