UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
4-7
4: Operation
Misc. sub-menu
4.4.3 UPS Setup Menu
The UPS Setup menu is used to set-up various UPS operating parameters and functions. This menu can be
password protected to prevent unauthorised access – see
’Operator Panel sub-menu’
on page 4-10.
Output sub-menu
Frequency:
This can be set to a nominal value (i.e. 50Hz or 60Hz) or it can be configured as AUTO whereby
the UPS output frequency synchronises to the input mains frequency and changes to the nominal value (50/
60Hz) if the input mains supply fails.
N+x Redundancy:
Where a system is designed to incorporate a number of redundant power modules, the
UPS contains more power modules than is required to power the full connected load. Therefore the system
could lose one (or more) power module before its ability to provide full load power is affected.
The
N+x Redundancy
setting determines the number of modules that can be inoperative before the system
sounds the
OUT OF REDUNDANCY
alarm. A practical example is shown in the table below:
Input sub-menu
PLL Enable:
If enabled, the UPS synchronises the output frequency to the input frequency. If disabled, the
UPS output frequency is not synchronised, the Green status led flashes and the ‘automatic bypass’ facility is
inhibited which means that the load is not fully protected in the event of a UPS fault or overload condition.
Extended PLL Range:
When enabled, the UPS output frequency synchronisation range is ±14% of the
nominal input frequency. When disabled this is reduced to ±2%.
Load (kW)
Fitted Power
Modules
Total Available
Power
Redundant
Modules
Redundant Alarm
Level (W)
System Overload
Level (W)
3700
3
3750
0
no
3750
3700
4
5000
1
3750
5000
1500
4
5000
2
2500
5000
1000
4
5000
3
1250
5000
UPS Status
UPS Setup
Events
Scheduling
Tools
MAIN MENU
UPS STATUS
UPS Info
Output
Input
Batteries
History Data
Misc.
MISC.
Int. Temp
xx
Ext. Temp
xx
Fan Speed
xx
UPS Internal termperature (deg C.)
UPS External termperature (deg C.)
Percentage fan speed (max 100)
UPS Status
UPS Setup
Events
Scheduling
Tools
MAIN MENU
OUTPUT
Voltage
Frequency
N+x Redundancy
Set the UPS output voltage
Set the UPS output frequency (nom/auto)
Set the number of redundant power boards
UPS SETUP
Output
Input
Bypass
Neutral Sensor
Batteries
Clock Setup
Operator Panel
UPS Status
UPS Setup
Events
Scheduling
Tools
MAIN MENU
INPUT
PLL Enable
Extend PLL Range
Enables UPS output to sync with mains
Sets the UPS output synch window
UPS SETUP
Output
Input
Bypass
Neutral Sensor
Batteries
Clock Setup
Operator Panel
Summary of Contents for Minipower Plus Rack
Page 1: ...Pioneering solutions for total power protection MINIpower PLUS User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 26: ...3 Installation 3 12 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 40: ...5 Maintenance 5 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...
Page 42: ...6 Troubleshooting 6 2 UPS453 01 00 MINIpowerPLUS User Manual Dated 08 03 12 ...