Overview 

The ERM consists of two battery packs in a 3U chassis. The 
ERM connects directly to a UPS R5500 or to another ERM. Up 
to two ERM units can be connected.  

At the HP recommended 80 percent load, one ERM extends 
the available UPS runtime up to 30 minutes. 

For more information about any of the topics covered in this 
document, see the UPS user guide located on the 
documentation CD or HP website 
(http://www.hp.com/go/rackandpower). 

 

Precautions 

  

WARNING:  A risk of personal injury from 

electric shock and hazardous energy levels 
exists. The installation of options and routine 
maintenance and service of this product 
must be performed by individuals who are 
knowledgeable about the procedures, 
precautions, and hazards associated with AC 
power products. 

  

 

75 kg 

167 lb 

This symbol indicates that the ERM 
exceeds the recommended weight for 
one individual to handle safely. 

WARNING: 

 To reduce the risk of 

personal injury or damage to the 
equipment, observe local occupational 
health and safety requirements and 
guidelines for manual material 
handling. 

  

CAUTION:

  Always plan the rack installation so that 

the heaviest item is on the bottom of the rack. Install 
the heaviest item first, and continue to populate the 
rack from the bottom to the top. 

 

ERM kit contents 

 

Important Safety Information

 guide 

 

This document 

 

Warranty information 

 

Rails, with mounting hardware for square- and  
round-holed racks 

 

ERM 

 

Front bezel 

 

Rear mounting brackets, plates, and  
associated hardware 

 

 

Summary of Contents for UPS R5500 ERM

Page 1: ...nance and service of this product must be performed by individuals who are knowledgeable about the procedures precautions and hazards associated with AC power products 75 kg 167 lb This symbol indicates that the ERM exceeds the recommended weight for one individual to handle safely WARNING To reduce the risk of personal injury or damage to the equipment observe local occupational health and safety...

Page 2: ...ections to the branch circuit such as the use of power strips Electrical requirements All models require a dedicated unshared branch circuit suitably rated for the specific UPS as stated in Input specifications in the user guide Readying the equipment 1 Check the battery recharge date specified on the label that is affixed to the shipping carton IMPORTANT Do not use the battery if the recharge dat...

Page 3: ... rails for integrated shipping If the unit is to be shipped in an HP 9000 or 10000 series rack 1 Remove the hex nuts flat washers and lock washers from the mounting rail 2 Install the rail reinforcement plates and tighten using the hex nuts with captive washers included in the kit instead of the nuts included with the rail 3 Install the rear mounting brackets using hex nuts Wait until the unit is ...

Page 4: ... a hazardous condition CAUTION Always plan the rack installation so that the heaviest item is on the bottom of the rack Install the heaviest item first and continue to populate the rack from the bottom to the top 1 Install the mounting rails Installing the mounting rails on page 2 2 With one person on each side of the carton lift the chassis and lower it to the floor in front of the rack 3 Install...

Page 5: ...t parameter Available settings Parameter Associated LED Explanation when LED is illuminated Nominal Voltage Setting 200 208 Nom General Alarm red Nominal utility voltage level is set to 200 208 VAC factory default for 326529 D71 220 Nom On Battery red Nominal utility voltage level is set to 220 VAC 230 Nom Battery Fault red Nominal utility voltage level is set to 230 VAC factory default for 326529...

Page 6: ...onfigure mode press the Test Alarm Reset button NOTE Configure mode times out after 2 minutes If the Test Alarm Reset button has not been pressed any new selections are not saved UPS front panel controls The front panel is shown with the bezel removed Item Description Function 1 On button Powers up the UPS 2 Standby button Places the UPS in Standby mode 3 Test Alarm Reset button Silences UPS alarm...

Reviews: