background image

Underhill   ICC   Decoder   Module   Troubleshooting   Guide   

13   

Observed   Field   Condition   

10)   “I   have   one   or   more   stations   that   won’t   operate.      How   can   I   troubleshoot   this   field   

issue?”         

   

Possible   Causes   

The   solenoid   has   reached   the   end   of   its   service   life   
The   decoder   has   reached   the   end   of   its   service   life   
There   is   a   break   in   the   2Wire   path   to   this   valve   due   to   how   the   wire   path   is   installed.      

   

How   to   Troubleshoot   

1)

 

Determine   if   the   inoperable   stations   are   in   numerical   order.      For   example   

stations   07-­‐11   don’t   operate.      If   this   condition   exists,   then   a   broken   2Wire   com   
path   may   exist.      If   the   inoperable   stations   are   random   than   follow   steps   2-­‐4.   

2)

 

   Disconnect   the   decoder   from   the   valve   solenoid.      Using   a   multi-­‐meter,   conduct   
an   ohm   resistance   test   on   the   valve   solenoid.      The   reading   should   be   24-­‐30   
ohms   indicating   an   acceptable   and   working   solenoid.      If   the   ohm   reading   is   

higher,   then   the   solenoid   may   require   replacement.      Compare   this   reading   
against   a   known   working   solenoid   before   moving   to   the   next   troubleshooting   

task.      

3)

 

Disconnect   the   decoder   and   use   a   known   working   solenoid   (typically   a   spare   
service   part).      Temporarily   disconnect   the   2Wire   path   from   the   ICC   decoder   

module   labeled   L1/   L2.      Connect   the   red   and   black   wires   of   the   decoder   and   
then   connect   the   known   working   solenoid   to   either   yellow   wire.      Turn   this   
corresponding   station   on   via   the   “Manual   –   Single   Station”   function.      If   the   

solenoid   does   not   “buzz”   then   verify   the   decoder   is   programmed   correctly.      If   
the   decoder   “buzzes”   then   you   may   have   a   broken   2Wire   com   wire.   

4)

 

Look   around   to   determine   if   any   ground   disturbance   can   be   located   that   might   
indicate   a   break   in   the   2Wire   path.   Use   a   digital   clamp   meter   and   portable   
power   supply   to   locate   the   break   and   repair   as   needed.      Stringing   a   temporary   

pair   of   wires   from   the   nearest   valve   box   to   confirm   the   valve   and   decoder   
operation   is   another   alternative   isolating   method.      

   

Observed   Field   Condition   

11)   “I   just   replaced   the   Underhill   ICC   decoder   module,   do   I   need   to   reprogram   all   of   the   

decoders?”         

   

Solution   

No,   the   station   number   is   retained   in   the   decoder   once   programmed.      The   default   
station   number   of   any   “new”   decoder   is   01.         

   

Summary of Contents for ICC 2 Wire

Page 1: ...rate station 08 from the 2Wire Decoder 9 5 The Hunter ICC is using 11 stations with two station modules and this installation also has an Underhill 2Wire module in the third space I cannot operate sta...

Page 2: ...m the Hunter ICC controller I need to add a new station which I connected to the wire path for the master valve with a decoder but the station does not operate I can hear the solenoids buzzing but nei...

Page 3: ...erly and operating a Locate press and hold the Reset button on the ICC Decoder Module as shown for approximately 10 seconds The Green Accept LED should blink on and off for approximately 15 20 seconds...

Page 4: ...r If the station does not operate remove a decoder from a valve box assuming it has already been programmed and connect the red and black decoder wires into the L1 L2 terminals on the ICC Decoder modu...

Page 5: ...y be displayed as 100 Ohms or higher Replace the solenoid if needed e If after attempting steps 3 4 without success remove AC power and the 9 volt back up battery if it exists from the ICC controller...

Page 6: ...d local distributor 2 Is a 8 or 10 bare copper wire terminated in the Ground terminal to a ground rod or ground plate if only the ICC Decoder Module is installed If the ICC controller is being used wi...

Page 7: ...ire connection using the included 3M DBRY connectors for a waterproof wire connection 5 If after all of these tasks the error LED on the decoder module continues to remain on then use a multi meter an...

Page 8: ...it to station 10 s location and try again If it does not operate there is a break in the 2Wire com path and a you ll need a digital Clamp Meter Underhill p n TW DCM to determine where the break has oc...

Page 9: ...en programed from 12 16 and re program to stations higher than the last station using station decoders Confirm their operation by operating in MANUAL mode once re installed Observed Field Condition 6...

Page 10: ...ble Causes The Hunter ICC controller and the Underhill ICC decoder module are not synchronized or something has occurred to the programming function in the ICC decoder module How to Troubleshoot 1 Tur...

Page 11: ...ted to a Roam or Roam XL hand held receiver or Solar Sync How to Troubleshoot Verify if a blue colored capacitor has been installed on the Hunter ICC s power module Generally if this capacitor is miss...

Page 12: ...wires of the decoder into either one of these connections Attach the two yellow wires of the decoder to a known working solenoid Attempt to operate the corresponding station number manually from the H...

Page 13: ...id before moving to the next troubleshooting task 3 Disconnect the decoder and use a known working solenoid typically a spare service part Temporarily disconnect the 2Wire path from the ICC decoder mo...

Page 14: ...you see the green LED flash see figure below Then turn the main menu knob on the Hunter ICC to the RUN position and observe the green LED flashing again Press and hold the Reset Button on the ICC Dec...

Page 15: ...ire reprogramming Observed Field Condition 14 I m new to this site and there are no As built drawings denoting the valve locations I can t locate or irrigate some stations Will a cable detector I use...

Page 16: ...erify the decoder has been programmed to the appropriate station number and retry If the valve operates as well as the master valve then trench and bury the temporary 2Wire path Observed Field Conditi...

Page 17: ...ne of more has a defective decoder and or solenoid Remember as a solenoid reaches end of life it has more resistance drawing excessive current How To Troubleshoot Damaged decoders typically take a low...

Page 18: ...module Using the clamp meter and clamp around one of the conductors on the 2Wire path then operate station 01 manually from the ICC controller Write down the mA value displayed on the clamp meter and...

Page 19: ...d from the L1 L2 terminals and connected directly to the 24 volt terminal block of the Hunter ICC power module This is done with the 120 volt power to the ICC controller Off Stations will not operate...

Page 20: ...he field Temporarily disconnect station 07 decoder and re attach the 2Wire path essentially bypassing station 07 2 Operate station 08 and others and confirm they operate individually If they do then r...

Reviews: