Underhill   ICC   Decoder   Module   Troubleshooting   Guide   

17   

   

Program   the   controller   to   turn   on   the   pump/master   valve   output   along   with   several   
stations   from   a   programmed   start   time.         As   stations   are   operating,   measure   the   

current   draw   along   the   2Wire   path.   
            
This   may   require   disconnecting   half   the   stations   or   a   branch   in   the   2Wire   path   to   

isolate   a   decoder(s).      Remove   and   replace   the   located   decoders   as   needed.      Remember   
to   program   them   with   the   corresponding   station   number   first.         

   

Observed   Field   Condition   

17)   “I   replaced   the   ICC   module   recently   and   came   back   to   the   controller   only   to   

determine   the   ICC   module   is   no   longer   operating.      Why   do   I   keep   “blowing-­‐up”   ICC   

modules?”   

   

Possible   Causes   

1)   The   ICC   module   is   not   grounded   to   a   separate   ground   rod,   (not   electrical   ground   
but   “earth-­‐ground”.   

2)   You   may   have   several   decoders   with   the   same   address   and   one   of   more   has   a   
defective   decoder   and/or   solenoid.      (Remember   as   a   solenoid   reaches   end-­‐of-­‐life,   it   has   

more   resistance   drawing   excessive   current).   

 

How   To   Troubleshoot   

Damaged   decoders   typically   take   a   lower   or   higher   current   than   the   2.9   to   3.1   mA   

values.         
1)

 

Confirm   the   ICC   module   has   a   #12   solid   copper   ground   wire   to   a   ground   rod   or   
ground   plate.      The   ground   rod   should   be   a   copper-­‐clad   8”   long   x   5/8”   diameter   

ground   rod   driven   full-­‐depth.      Connect   the   ground   wire   without   any   sharp   bends   or   
angles.      If   local   soil   conditions   prevent   installation   of   a   ground   rod,   consider   using   

a   ground   plate.      Both   should   be   installed   a   minimum   of   10’   away   from   the   
controller.      Sometimes   site   conditions   prevent   this   distance   so   shorter   distances   are   
acceptable   as   exception   not   the   rule.         

   

2)

 

To   troubleshoot   the   2Wire   path   you   will   need   the   following   troubleshooting   
equipment:   

   

Fault-­‐finding   transformer      

Digital   Clamp   Leak   Detector   

Underhill   p/n   TRANSFRMR-­‐115V   

Underhill   p/n   TW-­‐DCM   

   

   

   

 

Temporarily   disconnect   the   2Wire   path   connected   to   L1/L2   on   the   decoder   

module.         

Summary of Contents for ICC 2 Wire

Page 1: ...rate station 08 from the 2Wire Decoder 9 5 The Hunter ICC is using 11 stations with two station modules and this installation also has an Underhill 2Wire module in the third space I cannot operate sta...

Page 2: ...m the Hunter ICC controller I need to add a new station which I connected to the wire path for the master valve with a decoder but the station does not operate I can hear the solenoids buzzing but nei...

Page 3: ...erly and operating a Locate press and hold the Reset button on the ICC Decoder Module as shown for approximately 10 seconds The Green Accept LED should blink on and off for approximately 15 20 seconds...

Page 4: ...r If the station does not operate remove a decoder from a valve box assuming it has already been programmed and connect the red and black decoder wires into the L1 L2 terminals on the ICC Decoder modu...

Page 5: ...y be displayed as 100 Ohms or higher Replace the solenoid if needed e If after attempting steps 3 4 without success remove AC power and the 9 volt back up battery if it exists from the ICC controller...

Page 6: ...d local distributor 2 Is a 8 or 10 bare copper wire terminated in the Ground terminal to a ground rod or ground plate if only the ICC Decoder Module is installed If the ICC controller is being used wi...

Page 7: ...ire connection using the included 3M DBRY connectors for a waterproof wire connection 5 If after all of these tasks the error LED on the decoder module continues to remain on then use a multi meter an...

Page 8: ...it to station 10 s location and try again If it does not operate there is a break in the 2Wire com path and a you ll need a digital Clamp Meter Underhill p n TW DCM to determine where the break has oc...

Page 9: ...en programed from 12 16 and re program to stations higher than the last station using station decoders Confirm their operation by operating in MANUAL mode once re installed Observed Field Condition 6...

Page 10: ...ble Causes The Hunter ICC controller and the Underhill ICC decoder module are not synchronized or something has occurred to the programming function in the ICC decoder module How to Troubleshoot 1 Tur...

Page 11: ...ted to a Roam or Roam XL hand held receiver or Solar Sync How to Troubleshoot Verify if a blue colored capacitor has been installed on the Hunter ICC s power module Generally if this capacitor is miss...

Page 12: ...wires of the decoder into either one of these connections Attach the two yellow wires of the decoder to a known working solenoid Attempt to operate the corresponding station number manually from the H...

Page 13: ...id before moving to the next troubleshooting task 3 Disconnect the decoder and use a known working solenoid typically a spare service part Temporarily disconnect the 2Wire path from the ICC decoder mo...

Page 14: ...you see the green LED flash see figure below Then turn the main menu knob on the Hunter ICC to the RUN position and observe the green LED flashing again Press and hold the Reset Button on the ICC Dec...

Page 15: ...ire reprogramming Observed Field Condition 14 I m new to this site and there are no As built drawings denoting the valve locations I can t locate or irrigate some stations Will a cable detector I use...

Page 16: ...erify the decoder has been programmed to the appropriate station number and retry If the valve operates as well as the master valve then trench and bury the temporary 2Wire path Observed Field Conditi...

Page 17: ...ne of more has a defective decoder and or solenoid Remember as a solenoid reaches end of life it has more resistance drawing excessive current How To Troubleshoot Damaged decoders typically take a low...

Page 18: ...module Using the clamp meter and clamp around one of the conductors on the 2Wire path then operate station 01 manually from the ICC controller Write down the mA value displayed on the clamp meter and...

Page 19: ...d from the L1 L2 terminals and connected directly to the 24 volt terminal block of the Hunter ICC power module This is done with the 120 volt power to the ICC controller Off Stations will not operate...

Page 20: ...he field Temporarily disconnect station 07 decoder and re attach the 2Wire path essentially bypassing station 07 2 Operate station 08 and others and confirm they operate individually If they do then r...

Reviews: