background image

Underhill   ICC   Decoder   Module   Troubleshooting   Guide   

18   

 

Connect   the   2Wire   path   to   the   fault-­‐finding   transformer   (yellow   box   above).      

Clamp   the   red   lead   wire   from   the   fault-­‐finding   transformer   at   least   one   foot   

away   from   the   transformer.      

 

Measure   the   current   with   the   clamp   meter   along   the   2Wire   path   at   the   valve   

closest   to   the   controller   and   at   the   valve   furthest   away.      The   value   you   measure   
is   the   number   of   decoders   x   3mA.      For   example,   if   the   controller   is   managing   30   
stations,   then   a   value   of   around   90   mA   should   be   observed.      If   the   value   is   

initially   95   mA   at   the   station   closest   to   the   controller   but   0mA   at   the   valve   
furthest   away,   then   there   is   a   break   in   the   2Wire   path.      Measuring   at   intervals   
along   the   2Wire   path   will   indicate   where   the   short   lies.      If   the   value   measured   

at   the   valve   furthest   away   is   generally   the   same,   then   there   is   no   short   on   the   
2Wire   path.         

 

Disconnect   the   fault-­‐finding   transformer   from   the   2Wire   path   and   reconnect   

the   2Wire   path   to   the   L1/L2   terminals   on   the   decoder   module.         

 

Using   the   clamp   meter   and   clamp   around   one   of   the   conductors   on   the   2Wire   

path,   then   operate   station   01   manually   from   the   ICC   controller.      Write   down   

the   mA   value   displayed   on   the   clamp   meter   and   repeat   the   process   for   every   
station   on   the   2Wire   path.      If   the   red   “Error”   LED   comes   on,   reset   it   and   
continue   this   task.      Mark   the   station(s)   with   the   “Error”   message.      The   

corresponding   decoder   may   need   to   removed   and   verified   its   working   by   taking   
it   back   to   the   ICC   module   and   operating   it   in   Manual   –   Single   Station   mode   
with   a   known   working   solenoid.      If   it   does   not   operate,   then   replace.      While   the   

decoder   is   removed,   conduct   an   ohms   check   on   the   valve   solenoid   to   verify   it’s   
functioning.      Generally   a   “good”   solenoid   will   have   a   value   between   25-­‐35.      If   

the   value   is   much   higher,   replace   the   solenoid.      

 

You   may   encounter   more   that   one   station   being   managed   by   a   single   decoder   

or   several   decoders   with   the   same   address.         

 

Temporarily   disconnect   one   of   the   solenoids   from   the   decoder   and   operate   the   

station   manually   again.      Write   down   this   value.      Using   the   clamp   meter,   
conduct   an   ohms   test   on   the   disconnected   solenoid.         

 

Repeat   the   process   on   the   other   solenoid   sharing   the   same   decoder.      Replace   if   

necessary.         

   

Summary of Contents for ICC 2 Wire

Page 1: ...rate station 08 from the 2Wire Decoder 9 5 The Hunter ICC is using 11 stations with two station modules and this installation also has an Underhill 2Wire module in the third space I cannot operate sta...

Page 2: ...m the Hunter ICC controller I need to add a new station which I connected to the wire path for the master valve with a decoder but the station does not operate I can hear the solenoids buzzing but nei...

Page 3: ...erly and operating a Locate press and hold the Reset button on the ICC Decoder Module as shown for approximately 10 seconds The Green Accept LED should blink on and off for approximately 15 20 seconds...

Page 4: ...r If the station does not operate remove a decoder from a valve box assuming it has already been programmed and connect the red and black decoder wires into the L1 L2 terminals on the ICC Decoder modu...

Page 5: ...y be displayed as 100 Ohms or higher Replace the solenoid if needed e If after attempting steps 3 4 without success remove AC power and the 9 volt back up battery if it exists from the ICC controller...

Page 6: ...d local distributor 2 Is a 8 or 10 bare copper wire terminated in the Ground terminal to a ground rod or ground plate if only the ICC Decoder Module is installed If the ICC controller is being used wi...

Page 7: ...ire connection using the included 3M DBRY connectors for a waterproof wire connection 5 If after all of these tasks the error LED on the decoder module continues to remain on then use a multi meter an...

Page 8: ...it to station 10 s location and try again If it does not operate there is a break in the 2Wire com path and a you ll need a digital Clamp Meter Underhill p n TW DCM to determine where the break has oc...

Page 9: ...en programed from 12 16 and re program to stations higher than the last station using station decoders Confirm their operation by operating in MANUAL mode once re installed Observed Field Condition 6...

Page 10: ...ble Causes The Hunter ICC controller and the Underhill ICC decoder module are not synchronized or something has occurred to the programming function in the ICC decoder module How to Troubleshoot 1 Tur...

Page 11: ...ted to a Roam or Roam XL hand held receiver or Solar Sync How to Troubleshoot Verify if a blue colored capacitor has been installed on the Hunter ICC s power module Generally if this capacitor is miss...

Page 12: ...wires of the decoder into either one of these connections Attach the two yellow wires of the decoder to a known working solenoid Attempt to operate the corresponding station number manually from the H...

Page 13: ...id before moving to the next troubleshooting task 3 Disconnect the decoder and use a known working solenoid typically a spare service part Temporarily disconnect the 2Wire path from the ICC decoder mo...

Page 14: ...you see the green LED flash see figure below Then turn the main menu knob on the Hunter ICC to the RUN position and observe the green LED flashing again Press and hold the Reset Button on the ICC Dec...

Page 15: ...ire reprogramming Observed Field Condition 14 I m new to this site and there are no As built drawings denoting the valve locations I can t locate or irrigate some stations Will a cable detector I use...

Page 16: ...erify the decoder has been programmed to the appropriate station number and retry If the valve operates as well as the master valve then trench and bury the temporary 2Wire path Observed Field Conditi...

Page 17: ...ne of more has a defective decoder and or solenoid Remember as a solenoid reaches end of life it has more resistance drawing excessive current How To Troubleshoot Damaged decoders typically take a low...

Page 18: ...module Using the clamp meter and clamp around one of the conductors on the 2Wire path then operate station 01 manually from the ICC controller Write down the mA value displayed on the clamp meter and...

Page 19: ...d from the L1 L2 terminals and connected directly to the 24 volt terminal block of the Hunter ICC power module This is done with the 120 volt power to the ICC controller Off Stations will not operate...

Page 20: ...he field Temporarily disconnect station 07 decoder and re attach the 2Wire path essentially bypassing station 07 2 Operate station 08 and others and confirm they operate individually If they do then r...

Reviews: