Underhill   ICC   Decoder   Module   Troubleshooting   Guide   

12   

Observed   Field   Condition   

9)   “There   are   two   solenoids   sharing   a   single   decoder.      All   other   stations   operate,   but   

neither   one   of   these   valves   will   operate   in   a   Manual   or   scheduled   irrigation   mode.”         

   

Possible   Causes   

One   of   several   issues   may   have   occurred:   

1)

 

The   decoder   has   failed   or   is   not   programmed   to   the   corresponding   station   
number   on   the   controller’s   station   output.   

2)

 

One   or   both   of   the   solenoids   has   failed   

3)

 

There   is   a   field   wiring   issue   in   the   2Wire   communication   cable   between   the   
controller   and   this   station.      There   could   be   a   splice   in   the   2Wire   path   off   of   the   

main   2Wire   com   path   run   to   this   station   specifically.      

   

How   to   Troubleshoot   

Each   of   the   three   possible   causes   can   be   diagnosed   in   the   following   order;   

1)

 

Removed   the   corresponding   decoder   from   the   two   valve   solenoids   and   bring   

back   to   the   controller.      Temporarily   disconnect   the   2Wire   com   cable   wires   from   
L1/L2   and   connect   the   black   and   red   wires   of   the   decoder   into   either   one   of   

these   connections.      Attach   the   two   yellow   wires   of   the   decoder   to   a   known   
working   solenoid.      Attempt   to   operate   the   corresponding   station   number   
manually   from   the   Hunter   ICC   controller.      If   the   solenoid   does   not   “buzz”,   then   

try   a   working   decoder.      You   might   also   re-­‐program   the   decoder   to   the   
corresponding   station   number   and   retry   step   #1.   

2)

 

If   the   solenoid   buzzes,   then   isolate   the   mainline   and   remove   both   solenoids   

from   the   field   where   the   decoder   was   originally   installed.      Connect   one   of   the   
solenoids   to   the   decoder   still   attached   to   the   L1/L2   terminals.      Attempt   to   

operate   this   station   manually.      If   the   solenoid   “buzzes”,   then   retry   with   the   
second   solenoid.      If   it   too   “buzzes”   then   wire   them   both.      If   both   “buzz”   then   go   
to   #3.      If   one   solenoid   “buzzes”   and   the   other   does   not,   replace   the   solenoid   that   

did   not   originally   “buzz”.   

3)

 

If   both   solenoid   “buzzed”   in   #2   but   won’t   once   re-­‐installed   in   the   valve   box,   then   

a   problem   exists   in   the   two-­‐wire   path   somewhere   between   the   controller   and   
this   set   of   valves.      Purchase   a   digital   clamp   meter   Underhill   p/n   TW-­‐DCM   and   
portable   power   supply   Underhill   p/n   TRANSFRMR-­‐115   to   locate   the   field   issue.   

   

Summary of Contents for ICC 2 Wire

Page 1: ...rate station 08 from the 2Wire Decoder 9 5 The Hunter ICC is using 11 stations with two station modules and this installation also has an Underhill 2Wire module in the third space I cannot operate sta...

Page 2: ...m the Hunter ICC controller I need to add a new station which I connected to the wire path for the master valve with a decoder but the station does not operate I can hear the solenoids buzzing but nei...

Page 3: ...erly and operating a Locate press and hold the Reset button on the ICC Decoder Module as shown for approximately 10 seconds The Green Accept LED should blink on and off for approximately 15 20 seconds...

Page 4: ...r If the station does not operate remove a decoder from a valve box assuming it has already been programmed and connect the red and black decoder wires into the L1 L2 terminals on the ICC Decoder modu...

Page 5: ...y be displayed as 100 Ohms or higher Replace the solenoid if needed e If after attempting steps 3 4 without success remove AC power and the 9 volt back up battery if it exists from the ICC controller...

Page 6: ...d local distributor 2 Is a 8 or 10 bare copper wire terminated in the Ground terminal to a ground rod or ground plate if only the ICC Decoder Module is installed If the ICC controller is being used wi...

Page 7: ...ire connection using the included 3M DBRY connectors for a waterproof wire connection 5 If after all of these tasks the error LED on the decoder module continues to remain on then use a multi meter an...

Page 8: ...it to station 10 s location and try again If it does not operate there is a break in the 2Wire com path and a you ll need a digital Clamp Meter Underhill p n TW DCM to determine where the break has oc...

Page 9: ...en programed from 12 16 and re program to stations higher than the last station using station decoders Confirm their operation by operating in MANUAL mode once re installed Observed Field Condition 6...

Page 10: ...ble Causes The Hunter ICC controller and the Underhill ICC decoder module are not synchronized or something has occurred to the programming function in the ICC decoder module How to Troubleshoot 1 Tur...

Page 11: ...ted to a Roam or Roam XL hand held receiver or Solar Sync How to Troubleshoot Verify if a blue colored capacitor has been installed on the Hunter ICC s power module Generally if this capacitor is miss...

Page 12: ...wires of the decoder into either one of these connections Attach the two yellow wires of the decoder to a known working solenoid Attempt to operate the corresponding station number manually from the H...

Page 13: ...id before moving to the next troubleshooting task 3 Disconnect the decoder and use a known working solenoid typically a spare service part Temporarily disconnect the 2Wire path from the ICC decoder mo...

Page 14: ...you see the green LED flash see figure below Then turn the main menu knob on the Hunter ICC to the RUN position and observe the green LED flashing again Press and hold the Reset Button on the ICC Dec...

Page 15: ...ire reprogramming Observed Field Condition 14 I m new to this site and there are no As built drawings denoting the valve locations I can t locate or irrigate some stations Will a cable detector I use...

Page 16: ...erify the decoder has been programmed to the appropriate station number and retry If the valve operates as well as the master valve then trench and bury the temporary 2Wire path Observed Field Conditi...

Page 17: ...ne of more has a defective decoder and or solenoid Remember as a solenoid reaches end of life it has more resistance drawing excessive current How To Troubleshoot Damaged decoders typically take a low...

Page 18: ...module Using the clamp meter and clamp around one of the conductors on the 2Wire path then operate station 01 manually from the ICC controller Write down the mA value displayed on the clamp meter and...

Page 19: ...d from the L1 L2 terminals and connected directly to the 24 volt terminal block of the Hunter ICC power module This is done with the 120 volt power to the ICC controller Off Stations will not operate...

Page 20: ...he field Temporarily disconnect station 07 decoder and re attach the 2Wire path essentially bypassing station 07 2 Operate station 08 and others and confirm they operate individually If they do then r...

Reviews: