- 4 -
(2)Analog input(options: Type A2) Table.2
Survey type
Measurement deviation detection
Input level
DC4 to 20mA
Display interval
Fixed 0.5 seconds
Display accuracy
±0.3%F.S.±1digit
A/D bit conversion
About 7000 Resolution
A/D measurement interval
About 20ms
Temperature characteristic
±50ppm
Input impedance
Input resistance 250Ω
Measurement display range
0 to 9999
Setting range deviation upper
and lower limit
0 to 9999
Scaling (converter)
At analog MAX value, arbitrarily set in 0.001 to 9999
(3)Communication(Option:RS2、RS4、RS4W Type) Table.3
Signal level
RS2:EIA RS-232
standard
RS4(W)
:EIA RS-485
standard
Communication method
Half-duplex Communication method
Communication speed
2400bps/4800bps/9600bps/19200bps
Start bit
Fixed to 1 bit
Stop bit
Fixed to 1 bit
Data bit
7,8-bit mode switching
Parity bit
Nothing/Odd/Even setting
Transmitted and received data TOTAL display、PV display、SV Value setting
Analog display,Deviation(Upper limit・Lower limit)
Command method
Communication code
ASCII