Operating instructions for Heatermax Compact 10 / 20 Swimming Pool Heat Pumps

1

15

•  If the mains cable should be damaged, it must be replaced by a qualified electrician. Until then, the heat pump must be taken out of operation in order to prevent damage.
•   Switch off the power supply before you break current connections. Before you work on the pump, you must make sure that the power supply is switched off.
•   The device may not be installed near a heat source, inflammable material or the ventilation duct of an adjacent building.
•   The device is suitable for warming water in the operating range from min. 15°C to max. 35°C.
•   During the installation, repair and maintenance work, it is strictly prohibited to step on pipes and hoses, since they could be damaged and the coolant leaking out can cause serious burn injuries.
•   A filling of the device with the R32 coolant may be implemented only by an authorised specialist company.
•   In case of service work on the device, the composition and the status of the heat-transfer liquid must be tested. In addition, it must be ensured that, in case of welding and soldering work on the piping, no  

coolant is present in the heat pump. 

•   During the annual sealing test, which is implemented in accordance with the applicable legislation, the high-pressure and low-pressure switches must be tested in order to ensure that they are securely fixed on  

the cooling circuit and interrupt the electrical circuit when they are activated.

•   Before you begin with any work on the cooling circuit, please wait several minutes before you remove the temperature or pressure sensors. Certain component parts and lines can reach temperatures of over  

100°C and build up high pressures, which can lead to serious burn injuries.

•   This device includes component parts which are under pressure. Use only original spare parts and the R32 coolant, as indicated in the parts list of these directions for use and the rating plate.
•   Never use oxygen or dry air for the pressure test or in any search for leakage, since this introduces a fire or explosion hazard. Use nitrogen or the coolant indicated on the rating plate. The test pressure of the high- 
 

pressure, as well as the low-pressure circuit, may not exceed 42 bar.

•   This device can be used by children above 8 years, as well as by persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge, if they have been instructed in the safe use of  

the device and understand the hazards involved. Children may not play with the device. Cleaning and user maintenance may not be implemented by children without supervision.

•   Keep small parts and packaging material away from children. Danger of suffocation exists!

Utilisation

•   The Heatermax Compact swimming pool heat pump is planned for operation in combination with a pool pump and a filter, in order to warm up water in a swimming pool.
•   The following values for the water condition in the swimming pool must be adhered to:

 

 

- pH value 

 

 

 

 6.8 - < 7.6

 

 

- Free chlorine:  

 

 

< 3.0 mg/L

 

 

- Brom:  

 

 

 

< 5.0 mg/L

 

 

- Stabiliser (if used):  

 

 

< 75 mg/L

 

- Dissolved metals (iron, magnesium, copper, zinc ...):  

< 0.1 mg/L

•   The Heatermax Schwimmbecken heat pump is planned for private use only.

Operational start-up 

Attention! Do not lift the device on the outer casing. Use the base in order to lift and move the device.

Caution! This heat pump must be installed by a qualified specialist company. The installer is responsible for the device being installed correctly and the local regulations being adhered to. An 
incorrect installation of the device can have as consequence damage to the device and serious (possibly fatal) injuries.

Selection of the installation location

The heat pump can be installed at virtually any location in the open air, as long as the indicated minimum separation 
distances to other objects are adhered to (see drawing below). Ideally the heat pump should be installed with a separation 
distance of less than 7.5 m to the swimming pool. The greater the separation distance, the larger the heat loss in the water 
pipe from the heat pump to the swimming pool.

Installation of the device

• Place the device on a stable, solid, flat (concrete) underground.
• Ensure the device is not flooded by its own condensate water.

ATTENTION:

 Never install the heat pump in a closed room with limited air volume, in which the air discharged from the device is reused. Without a continuous fresh air supply, efficiency decreases and sufficient heat 

emission is prevented. 

Hydraulic connections

•  The Heatermax Compact swimming pool heat pump can usually be operated without a bypass. Install a bypass when the water flow of the swimming pool pump is more than 20% greater than the admissible 

flow through the heat exchanger of the heat pump.

•  Use a 38 mm or 32 mm PVC pool hose for the connections.
•  Secure the individual hose connections with a matching hose clamp.
•  When automatic dosing systems (chlorine, salt, etc.) are to be used, it is important to protect the heat pump against corrosion resulting from too high chemical concentrations. For this reason, such equipment 

must always be installed after the heat pump. It is recommended to install a non-return valve in order to prevent a return flow in case of lack of water circulation.

Remark: The delivery includes the heat pump exclusively. .

Electrical connections

Attention!

According to harmonised European directives and safety standards, the installation of the mains cable must 
be implemented by an authorised and qualified electrician.

•  The power supply must correspond to the product specifications. Do not connect the heat pump if the power 

supply does not correspond to the applicable regulations!

•  The power supply must be implemented over a residual-current device (Fi/RCD) with a rated leakage current 

of < 30 mA (pumps of Class 1).

•  If the mains cable and/or the power plug should be damaged, they must be replaced by a qualified electrician.

The hazard of electric shock exists in the interior of the device! The cables may be connected in 
the interior of the device by a qualified and authorised electrician only.

Heatermax COMPACT 10

Heatermax COMPACT 20

Summary of Contents for Heatermax Compact 10

Page 1: ...By Notice de montage Montageanleitung Opbouwinstructie Note of assembly Prospecto de montaje Avviso di montaggio ntage tung uctie mbly montaje taggio Pool COMPACT 10 20...

Page 2: ...u sonore un intervalle de 10 m 48 dB A 46 dB A Bo tier Acier inoxydable galvanis changeur thermique Titane dans r cipient en PVC Gaz de refroidissement R32 150 g 280 g Valeur GWP 675 675 quivalent CO2...

Page 3: ...aison avec une pompe de bassin et un filtre afin de r chauffer l eau dans le bassin Les valeurs suivantes concernant la qualit de l eau dans le bassin doivent tre respect es valeur pH 6 8 7 6 chlore l...

Page 4: ...puis quitter V rification de la temp rature ambiante et de la temp rature de l eau Appuyez sur pour demander la v rification des param tres Appuyez sur ou sur pour s lectionner le code d0 d1 Appuyez u...

Page 5: ...quats Garantie Une garantie de deux ans compter de la date d achat est accord e pour les d fauts de mat riaux et de fabrication de ce produit pouvant tre prouv s Pour pouvoir b n ficier de cette garan...

Page 6: ...B A 46 dB A Geh use verzinkter Stahl W rmetauscher Titan in PVC Beh lter K hlgas R32 150 g 280 g GWP Wert 675 675 CO2 quivalent 0 19 t 0 10 t L nge 310 mm 434 mm Breite 356 5 mm 432 5 mm H he 365 mm 4...

Page 7: ...freies Chlor 3 0 mg L Brom 5 0 mg L Stabilisator falls verwendet 75 mg L gel ste Metalle Eisen Magnesium Kupfer Zink 0 1 mg L Die Heatermax Schwimmbecken W rmepumpe ist nur f r den privaten Gebrauch v...

Page 8: ...len Bereich 10 42 C Dr cken Sie um die Einstellung zu speichern und dann zu beenden berpr fung der Umgebungs undWassertemperatur Dr cken Sie um die Parameter berpr fung aufzurufen Dr cken Sie oder um...

Page 9: ...rch unkontrollierte M llbeseitigung zu schaden Bitte entsorgen Sie Altger te deshalb ber geeignete Sammelsysteme Garantie F r dieses Produkt gilt eine Garantie von zwei Jahren ab Kaufdatum f r nachwei...

Page 10: ...A 46 dB A Behuizing Roestvrij gegalvaniseerd staal Warmtewisselaar Titanium in PVC reservoir Koelgas R32 150 g 280 g GWP waarde 675 675 CO2 equivalent 0 19 t 0 10 t Lengte 310 mm 434 mm Breedte 356 5...

Page 11: ...rde 6 8 7 6 Vrij chloor 3 0 mg l Broom 5 0 mg l Stabilisator indien gebruikt 75 mg l Opgeloste metalen ijzer magnesium koper zink 0 1 mg l De Heatermax warmtepomp voor zwembassins is alleen voorzien v...

Page 12: ...of direct op om de ingangstemperatuur van het water in te stellen bereik 10 C Druk op om de instelling op te slaan en dan te be indigen Controle van de omgevings en watertemperatuur Druk op om de para...

Page 13: ...engen Gooi oude apparaten daarom weg via geschikte inzamelsystemen Garantie Voor dit product geldt een garantie van twee jaar vanaf de aankoopdatum voor aantoonbare materiaal en productiefouten Het or...

Page 14: ...l at 1 m distance 57 dB A 55 dB A Noise level at 10 m distance 48 dB A 46 dB A Housing Rust free zinc coated steel Heat exchanger Titanium PVC container Cooling gas R32 150 g 280 g GWP value 675 675 C...

Page 15: ...be adhered to pH value 6 8 7 6 Free chlorine 3 0 mg L Brom 5 0 mg L Stabiliser if used 75 mg L Dissolved metals iron magnesium copper zinc 0 1 mg L The Heatermax Schwimmbecken heat pump is planned fo...

Page 16: ...ly in order to adjust water outlet temperature range 10 42 C Press to save the adjustment and then to end Verification of the ambient and water temperature Press in order to call up parameter verifica...

Page 17: ...le collection systems Guarantee For this product a guarantee of two years from purchase date applies for verifiable material and manufacturing faults In order to use this guarantee original proof of p...

Page 18: ...10 m de distancia 48 dB A 46 dB A Carcasa acero inoxidable galvanizado Intercambiador de calor Titanio en recipiente de PVC Gas refrigerador R32 150 g 280 g Valor GWP 675 675 Equivalencia CO2 0 19 t...

Page 19: ...una piscina Deben mantenerse los siguientes valores de calidad del agua en la piscina valor pH 6 8 7 6 cloro libre 3 0 mg L bromo 5 0 mg L estabilizador en caso de usarse 75 mg L metales disueltos hie...

Page 20: ...nde cuando se produce un c digo de error Pulse o directamente para ajustar la temperatura de salida del agua margen 10 42 C Pulse para memorizar el ajuste y finalizar Comprobaci n de la temperatura de...

Page 21: ...limine sus equipos desechados a trav s de puntos de recogida adecuados Garant a Este producto tiene una garant a de dos a os a partir de la fecha de compra que cubre fallos de material y fabricaci n v...

Page 22: ...A 46 dB A Alloggiamento acciaio zincato inossidabile Scambiatore di calore Titanio in contenitore PVC Gas refrigerante R32 150 g 280 g Valore GWP Potenziale di riscaldamento globale 675 675 CO2 equiv...

Page 23: ...seguenti valori di qualit dell acqua nella piscina valore del pH 6 8 7 6 Cloro libero 3 0 mg L Bromo 5 0 mg L Stabilizzatore se utilizzato 75 mg L Metalli sciolti ferro magnesio rame zinco 0 1 mg L La...

Page 24: ...concludere il processo Controllo della temperatura ambientale e dell acqua Premere per richiamare il controllo dei parametri Premere oppure per selezionare il codice d0 d1 Premere nuovamente per visu...

Page 25: ...anzia di questo prodotto ha una durata di due anni a partire dalla data di acquisto e copre difetti comprovabili di produzione e del materiale Affinch la garanzia sia valida necessario conservare la p...

Page 26: ......

Page 27: ...il verkoop outsideliving com Export Outside Living Industries Nederland B V Postbus 15 NL 1800 AA Alkmaar Berenkoog 87 NL 1822 BN Alkmaar Tel Sales 0031 0 72 5 671 661 Tel 0031 0 72 5 671 671 Fax 0031...

Page 28: ...www outsideliving com...

Reviews: