![Tyco Fire Suppression & Building Products ANSUL AQUASONIC Design, Installation, Recharge, And Maintenance Manual Download Page 9](http://html1.mh-extra.com/html/tyco-fire-suppression-and-building-products/ansul-aquasonic/ansul-aquasonic_design-installation-recharge-and-maintenance-manual_1186438009.webp)
Description
The cylinder is factory filled with nitrogen to a nominal pres-
sure of 2900 psi (200 bar). Multiple cylinders can be mani-
folded together to obtain the required quantity of nitrogen. The
cylinder valve can be actuated electrically, pneumatically,
and/or manually with approved valve actuation components.
All valves are equipped with an anti-recoil feature.
The cylinders are shipped with a maintenance record card
and protective shipping cap attached to the threaded neck
of each cylinder. This cap entirely encloses and protects the
valve while in shipment.
CV-98 INERGEN Valve
The CV-98 valve has a ten (10) year warranty.
The valve
requires no internal maintenance.
The valve is sealed
closed and must not be disassembled. If there is ever a
malfunction of the CV-98 valve, the complete valve must be
sent back to ANSUL for warranty replacement.
If the exter-
nal seal is broken, the warranty is voided.
Note:
Use Flexible Discharge Bend, Part No. 427082, when attaching
valve to supply pipe or manifold.
System Components
3-1-10
Page 1-2
TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI 54143
Form No. F-2010033 Copyright © 2010 Tyco Fire Suppression & Building Products. All rights reserved.
CV-98 Valve / Cylinder Shipping Assembly
Component
Material
Approvals
Cylinder
Steel
Meets DOT 3AA3000
or EN1964-2
Valve
Brass
Safety Relief Valve
Brass
Valve/Cylinder
—
FM Approved
Assembly
Shipping Cap
Steel
Shipping
Standardized Approximate
Amount
Dimension
Dimension
Assembly
Cylinder N
2
Capacity
Weight
of N
2
A
B
Part No.
ft
3
(m
3
)
lb
(kg)
lb
(kg)
in.
(cm)
in.
(cm)
DOT 437166
575
(16.3)
322
(146)
41.1
(18.6)
68.5 (174.0)
11.0
(27.9)
TPED 21741
561
(16.0)
229
(104)
40.0
(18.2)
68.0 (172.7)
10.5
(26.7)
PRESSURE
GAUGE
SAFETY
RELIEF
VALVE
002252
VALVE
HEIGHT TO OUTLET
CENTER
002251
RECORD
TAG
PRESSURE
GAUGE
CYLINDER
SHIPPING CAP
VALVE SHIPPING CAP
B
A
Summary of Contents for ANSUL AQUASONIC
Page 84: ...SECTION V 3 1 2010 Page 5 14 NOTES Installation ...
Page 88: ...SECTION VII 3 1 2010 Page 7 2 Inspection NOTES ...
Page 94: ...SECTION VIII 3 1 2010 Page 8 6 NOTES Maintenance ...
Page 116: ...APPENDIX C 3 1 2010 Page C 2 Main and Reserve Systems NOTES ...
Page 134: ...APPENDIX D 3 1 2010 Page D 18 008567 Typical Examples ...
Page 135: ...APPENDIX D 3 1 2010 Page D 19 008568 Typical Examples ...
Page 136: ...APPENDIX D 3 1 2010 Page D 20 008569 Typical Examples ...
Page 137: ...APPENDIX D 3 1 2010 Page D 21 008570 Typical Examples ...
Page 138: ...APPENDIX D 3 1 2010 Page D 22 008571 Typical Examples ...
Page 139: ...APPENDIX D 3 1 2010 Page D 23 008572 Typical Examples ...
Page 140: ...APPENDIX D 3 1 2010 Page D 24 008573 Typical Examples ...
Page 141: ...APPENDIX D 3 1 2010 Page D 25 008574 Typical Examples ...