![Tyco Fire Suppression & Building Products ANSUL AQUASONIC Design, Installation, Recharge, And Maintenance Manual Download Page 81](http://html1.mh-extra.com/html/tyco-fire-suppression-and-building-products/ansul-aquasonic/ansul-aquasonic_design-installation-recharge-and-maintenance-manual_1186438081.webp)
SECTION V
3-1-2010
Page 5-11
INSTALLING ACTUATOR
Pneumatic Actuation for CV-98 Valve
To install pneumatic actuation, complete the following steps:
1. Remove the 1/8 in. pipe plug from the 1/8 in. actuation
port.
2. Attach adaptor (Part No. 73236), male elbow (Part No.
32334), and 1/4 in. high pressure hose (depending on
length required, Part No. 31809, 32335 or 32336) to 1/4
in. actuation port. Securely tighten. See Figure 15.
FIGURE 15
007427a
3. Connect high pressure actuation piping to the outlet
port of ANSUL AUTOMAN II-C.
Electric Actuator
A maximum of two HF electric actuators can be installed on
a single AUTOPULSE release circuit.
Installing the Booster Actuator
1. Make certain the booster actuator is in the set (armed)
position. This can be confirmed by visually checking the
position of the top and bottom pins. When in the set
position, the top pin will be approximately flush with the
top of the actuator. The bottom pin will be flush with the
inside surface of the actuator. If the actuator requires
setting, use the arming tooling (Part No. 429847) and
follow the instructions listed in "Resetting the Booster
Actuator.”
2. Hand-tighten the actuator onto the cylinder valve.
See Figure 15 for installation details.
Installing the HF Actuator
1. Make certain the HF actuator is in the set (armed)
position. When in the set position, the top pin will be
flush with the top of the actuator. If the actuator
requires setting, use the arming tool (Part No. 75433)
and follow the instructions listed in "Resetting the HF
Actuator."
2. Hand-tighten the HF actuator onto the booster actuator.
3. If all other installations are complete, connect electrical
power to the HF actuator.
See Figure 15 for installation details.
Wiring for HF Actuator to AUTOPULSE Control Panel
Install wiring for HF actuators. Refer to HF Electric Actuator
Instruction Sheet (Part No. 73330) for detailed wiring infor-
mation.
Installation
CAUTION
!
Make certain all electric power from the panel to the
actuator has been disconnected. Failure to disconnect
power may cause accidental system discharge.
PNEUMATIC
ACTUATION
CHECK
VALVE,
PN25627
STRAIGHT
ADAPTOR,
PN32338
16” S.S.
BRAIDED
HOSE,
PN31809
MALE
ELBOW,
PN32334
CV-98
VALVE
PILOT VALVE ACTUATION
ADAPTOR, PN73236
CAUTION
!
Do not install the Booster Actuator onto nitrogen
cylinders at this time.
Summary of Contents for ANSUL AQUASONIC
Page 84: ...SECTION V 3 1 2010 Page 5 14 NOTES Installation ...
Page 88: ...SECTION VII 3 1 2010 Page 7 2 Inspection NOTES ...
Page 94: ...SECTION VIII 3 1 2010 Page 8 6 NOTES Maintenance ...
Page 116: ...APPENDIX C 3 1 2010 Page C 2 Main and Reserve Systems NOTES ...
Page 134: ...APPENDIX D 3 1 2010 Page D 18 008567 Typical Examples ...
Page 135: ...APPENDIX D 3 1 2010 Page D 19 008568 Typical Examples ...
Page 136: ...APPENDIX D 3 1 2010 Page D 20 008569 Typical Examples ...
Page 137: ...APPENDIX D 3 1 2010 Page D 21 008570 Typical Examples ...
Page 138: ...APPENDIX D 3 1 2010 Page D 22 008571 Typical Examples ...
Page 139: ...APPENDIX D 3 1 2010 Page D 23 008572 Typical Examples ...
Page 140: ...APPENDIX D 3 1 2010 Page D 24 008573 Typical Examples ...
Page 141: ...APPENDIX D 3 1 2010 Page D 25 008574 Typical Examples ...