Item
Description
Part no.
Air handling unit
Multileaf damper
Galvanised
steel
Stainless steel
Galvanised
steel
Stainless steel
⑩
Pan head screw M6
×
12
M852AC6
⑪
Socket cap head screw M6
×
30
M852AC4
1.
it with thread forming screws (Fig. 17/2), rubber seals (Fig. 17/4) and washers (Fig. 17/3).
Attaching the noise insulating connector to a multileaf damper
If the noise insulating connector is to be attached to a multileaf damper, fix it with the supplied socket cap
head screws (Fig. 17/5), rubber seals (Fig. 17/4), washers (Fig. 17/3 and 6) and nuts (Fig. 17/7).
2.
Fix one eye of the ground cable (Fig. 17/8) with a pan head screw M6
×
12 (Fig. 17/10) and a serrated lock
washer (Fig. 17/9) to the noise insulating connector.
NOTICE!
Electrical conductivity
For electrical conductivity the serrated lock washer needs to be fitted between the eye of the ground cable
and the coated surface.
3.
Fix the other eye of the ground cable with a socket cap head screw M6
×
30 (Fig. 17/11) and a serrated lock
washer through the panel sheet to the tubular frame of the air handling unit.
Setup and assembly
Setting up and assembling the air handling unit > Assembling AHU casing units
Air handling unit X-CUBE
27