Corrigo ver. no. 1.2-1-00

 

 
 
 

Topvex TR 03, TR04, TR06 

Compact Air Handling Unit 

 

 

 
 
 

 

 
 

 
 

 
 

 

 

 

 

 

Operation and Maintenance instructions

 

  

GB

  

GB

Summary of Contents for Topvex TR03

Page 1: ...Corrigo ver no 1 2 1 00 Topvex TR 03 TR04 TR06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Page 2: ...temair AB 2 Left model Right model Fig 1 Description 1 Connection Supply air 2 Connection Extract air 3 Connection Exhaust air 4 Connection Outside air 5 Supply air filter Topvex TR 04 6 Supply air fi...

Page 3: ...ructions 205353 Systemair AB 3 Fig 2 Description Description 1 Alarm button 7 Connection block 2 Alarm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button...

Page 4: ...rning the design installation start up and operation which shall be obeyed to ensure the proper fail free operation of the unit The key to proper and safe operating of the unit is to read this manual...

Page 5: ...ure is lower than the actual room temperature the actual room temperature is higher than the set room temperature limit The fans are stopped at the Stop Cooling Hour or if the following conditions are...

Page 6: ...buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the display To choose one use RIGHT again To back down to a l...

Page 7: ...or Manual shut off Service Login with 1111 to service level Log s out after 5 minutes of inactivity with main supply on Time Date Set the present time date and weekday Set the units ON time for each w...

Page 8: ...ol Recycling to Active or Not Active Preset is Not Active Function Starts the heat exchanger to recycling the cold extract air temperature when the extract temperature is 3K lower than the Outdoor air...

Page 9: ...r or Push button closes Only when the unit is running in Off mode DI4 Alarm VVX Stop the fans and close the dampers accessories when the alarm is activated DI5 Is only shown when the Fire function is...

Page 10: ...possible to set the output signal within a range from 0 to10V AO3 Control signal 0 10V to the supply and extract fan Show and Set the digital outputs output 24V AC DO1 Damper motor on off Opens the d...

Page 11: ...K button at the same time as the main voltage is switched on Change codeword Set a new code for Service level 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active M...

Page 12: ...l to clean the exchanger regularly to maintain high efficiency The heat exchanger can easily be taken out of the unit Wash in hot soapy water or use pressure air Do not use detergent containing ammoni...

Page 13: ...Exhaust air damper if used opens C Change of filters required D Cleaning of diffusers louvers required E Cleaning of fans exchanger block required F Is roof unit air intake clogged G Duct system Check...

Page 14: ...te 5 Product code specification Commissioning It is possible to manually regulate the set airflow with 2 potentiometers situated in the electrical compartment fig 7 This enables the fan motors to be r...

Page 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Page 16: ...t 12 0 C C Max supply set point 30 0 C C Air flow Fan speed Low 35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240...

Page 17: ...he rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www sy...