electrical
requirements
Installation
Table I-ER-8. Fan-coil electric heat kW
Unit Size
Unit Voltage
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
02
115
1.0
1.5
2.0
230
1.0
1.5
2.0
277
1.0
1.5
2.0
208
0.8
1.1
1.5
1.9
03
115
1.0
1.5
2.0
2.5
230
1.0
1.5
2.0
2.5
277
1.0
1.5
2.0
2.5
208
0.8
1.1
1.5
1.9
2.3
04
115
2.0
2.5
3.0
230
2.0
2.5
3.0
277
2.0
2.5
3.0
208
1.5
1.9
2.3
3.0
06
115
2.0
3.0
230
2.0
3.0
4.0
5.0
6.0
277
2.0
3.0
4.0
5.0
6.0
208
1.5
2.3
3.0
3.8
4.5
5.3
08
115
2.0
3.0
230
2.0
3.0
4.0
5.0
6.0
7.0
277
2.0
3.0
4.0
5.0
6.0
7.0
208
1.5
2.3
3.0
3.8
4.5
5.3
6.0
10
115
3.0
230
3.0
4.0
5.0
6.0
7.0
8.0
277
3.0
4.0
5.0
6.0
7.0
8.0
208
2.3
3.0
3.8
4.5
5.3
6.0
12
115
3.0
230
3.0
4.0
5.0
6.0
7.0
8.0
10.0
277
3.0
4.0
5.0
6.0
7.0
8.0
10.0
208
2.3
3.0
3.8
4.5
5.3
6.0
Table I-ER-9. Electric heat kW, low vertical fan-coils
unit size
unit voltage
kW
kW
kW
kW
03
115
1.0
1.5
2.0
04
115
1.0
1.5
2.0
2.5
06
115
1.0
1.5
2.0
2.5
Low vertical units are only available with electric heat in combination with the two-row cooling coil.
Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations for
Fan-Coils with Single Phase Electric Heat
Heater amps = (heater kW x 1000)/heater voltage
Note: Use 120V heater voltage for 115V units. Use 240V heater voltage for 230V units.
MCA = 1.25 x (heater amps + all motor FLAs)
MFS or HACR type circuit breaker = (2.25 x largest motor FLA) + second motor FLA
+ heater amps (if applicable)
HACR (heating, air-conditioning and refrigeration) type circuit breakers are required in
the branch circuit wiring for all fan-coils with electric heat.
Select a standard fuse size or HACR type circuit breaker equal to the MCA.
Use the next larger standard size if the MCA does not equal a standard size.
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60 amps
Fan-coil electric heat MBh = (heater kW) (3.413)
Summary of Contents for UniTrane FC
Page 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...
Page 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...
Page 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...
Page 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...
Page 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...
Page 77: ......
Page 78: ......
Page 79: ......