52
UNT-SVX07A-EN
Operation
sequence of
operation
Analog Inputs
Both Tracer ZN010 and ZN510 accept a
maximum of five analog inputs.
Reference Table O-SO-4.
Zone Sensors
The zone sensors available with the
Tracer ZN010 and ZN510 provide up to
three different inputs
1. Space temperature measurement
(10K
Ω
thermistor)
2. Local setpoint
3. Fan mode switch
Wall mounted zone sensors include a
thermistor as a component of the
internal printed circuit board. Unit
mounted zone sensors use a sensor
placed in the unit’s return air stream.
Each zone sensor is equipped with a
thumbwheel for setpoint adjustment.
Fan Mode Switch
The zone sensor may be equipped with a
fan mode switch. The fan mode switch
offers selections of off, low, medium,
high, or auto.
Supply Fan Operation
Reference Table O-SO-5 for fan mode
operation. Reference Table O-SO-5 for
fan mode operation. Tracer ZN010 and
ZN510 will operate in either continuous
fan or fan cycling mode. The fan cycles
when the fan mode switch is placed in
auto. The fan runs continuous when
placed in the high, medium, or low
position. Use Rover, Trane’s installation
and service tool, to change auto defaults.
Table O-SO-4. Analog inputs
analog input
description
application
zone
space temperature
space temperature detection
set
local setpoint
thumbwheel setpoint
fan
fan mode input
zone sensor fan switch
analog input 1 (AI1)
entering water temperature
entering water temperature detection
analog input 2 (AI2)
discharge air temperature discharge air temperature detection
Notes:
1.The zone sensor, entering water temperature sensor, and the discharge air temperature sensor are 10
K
Ω
thermistors.
Figure 26 provides the resistance-temperature curve for these thermistors.
2. Zone sensor:
Wall mounted sensors include a thermistor soldered to the sensor’s circuit board
Unit mounted sensors include a return air sensor in the unit’s return air stream.
3. Changeover units include an entering water temperature sensor.
Table O-SO-6. Valid operating range and factory default setpoints
setpoint/parameter
default setting
valid operating range
unoccupied cooling setpoint
85° F
40 to 115° F
occupied cooling setpoint
74° F
40 to 115° F
occupied heating setpoint
71° F
40 to 115° F
unoccupied heating setpoint
60° F
40 to 115° F
cooling setpoint high limit
110° F
40 to 115° F
cooling setpoint low limit
40° F
40 to 115° F
heating setpoint high limit
105° F
40 to 115° F
heating setpoint low limit
40° F
40 to 115° F
power-up control wait
0 sec 0 to 240 sec
Table O-SO-5. Fan mode operation
heating mode
cooling mode
fan mode
occupied
unoccupied
occupied
unoccupied
off
off
off
off
off
low
low
off/high (3)
low
off/high (3)
medium
medium
off/high (3)
medium
off/high (3)
high
high
off/high (3)
high
off/high (3)
auto
continuous
heat default
off/high (3)
cool default
off/high (3)
cycling off/heat default
off/high (3)
off/cool default
off/high (3)
Notes:
1. During the transition from off to any fan speed but high, Tracer ZN010 and ZN510 automatically starts the fan on high
speed and runs for three seconds before transitioning to the selected speed (if it is other than high). This provides
enough torque to start all fan motors from the off position.
2. When the heating output is controlled off, Tracer ZN010 and ZN510 automatically controls the fan on for an additional 30
seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.
3. Whenever two states are listed for the fan:
The first state (off) applies when there is not a call for heating or cooling.
The second state (varies) applies when there is a call for heating or cooling.
The heat default is factory configured for low fan speed, and the cool default is medium.
Summary of Contents for UniTrane FC
Page 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...
Page 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...
Page 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...
Page 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...
Page 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...
Page 77: ......
Page 78: ......
Page 79: ......