UNT-SVX07A-EN
7
Installation
general
information
Table I-GI-1. Fan-coil component data
unit size
02
03
04
06
08
10
12
Coil Data
Face Area — Ft
2
(cm
2
)
0.8 (743)
0.8 (743)
1.1 (1020)
1.6 (1490)
2.1 (1950)
3.2 (2970)
3.2 (2970)
LxDxH — In. (cm)
2-Row
15x1.7x8
15x1.7x8
20x1.7x8
29.5x1.7x8
38x1.7x8
57x1.7x8
57x1.7x8
(38x4x20)
(38x4x20)
(51x4x20)
(75x4x20)
(97x4x20)
(145x4x20)
(145x4x20)
3-Row
15x2.6x8
15x2.6x8
20x2.6x8
29.5x2.6x8
38x2.6x8
57x2.6x8
57x2.6x8
(38x7x20)
(38x7x20)
(51x7x20)
(75x7x20)
(97x7x20)
(145x7x20)
(145x7x20)
4-Row
15x3.5x8
15x3.5x8
20x3.5x8
29.5x3.5x8
38x3.5x8
57x3.5x8
57x3.5x8
(38x9x20)
(38x9x20)
(51x9x20)
(75x9x20)
(97x9x20)
(145x9x20)
(145x9x20)
Volume — Gal. (Liters)
1-Row (Heat)
.06 (.23)
.06 (.23)
.08 (.30)
.11 (.42)
.14 (.53)
.21 (.79)
.21 (.79)
2-Row
.12 (.45)
.12 (.45)
.15 (.57)
.22 (.83)
.28 (1.06)
.42 (1.59)
.42 (1.59)
3-Row
.18 (.68)
.18 (.68)
.23 (.87)
.33 (1.25)
.42 (1.59)
.62 (2.35)
.62 (2.35)
4-Row
.24 (.91)
.24 (.91)
.30 (1.14)
.44 (1.67)
.56 (2.12)
.83 (3.14)
.83 (3.14)
Fins/Ft (cm)
2-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
3-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
4-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
Reheat Coil Data (1-Row)
Hot Water or Steam
Face Area — Ft
2
(cm
2
)
0.6
0.6
0.8
1.2
1.6
2.4
2.4
(557)
(557)
(743)
(1120)
(1490)
(2230)
(2230)
LxDxH — In. (cm)
15x1.5x6
15x1.5x6
20x1.5x6
29.5x1.5x6
38x1.5x6
57x1.5x6
57x1.5x6
(38x4x15)
(38x4x15)
(51x4x15)
(75x4x15)
(97x4x15)
(145x4x15)
(145x4x15)
Volume — Gal. (Liters)
.12 (.45)
.12 (.45)
.15 (.57)
.22 (.83)
.28 (1.06)
.42 (1.59)
.42 (1.59)
Fins/Ft (cm)
48 (1.6)
48 (1.6)
48 (1.6)
48 (1.6)
48 (1.6)
48 (1.6)
48 (1.6)
Fan/Motor Data
Fan Quantity
1
1
1
2
2
3
3
Size — Dia” x Width” (cm)
6.31x4
6.31x6.5
6.31x7.5
6.31x6.5
6.31x7.5
(1) 6.31x7.5
6.31x7.5
(16x10)
(16x17)
(16x19)
(16x17)
(16x19)
(16x19)
(16x19)
Size — Dia” x Width” (cm)
(2) 6.31x6.5
(16x6.5)
Motor Quantity
1
1
1
1
1
2
2
Filter Data
1” (cm) TA and Pl. Media
Quantity
1
1
1
1
1
1
1
Size — In. (cm)
8
7
/
8
x 19
1
/
8
8
7
/
8
x 19
1
/
8
8
7
/
8
x 24
1
/
8
8
7
/
8
x 33
5
/
8
8
7
/
8
x 42
1
/
8
8
7
/
8
x 61
1
/
8
8
7
/
8
x 61
1
/
8
(23x49)
(23x49)
(23x61)
(23x85)
(23x107)
(23x155)
(23x155)
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity
1
1
1
1
1
1
1
Size — In. (cm)
5
1
/
2
x 19
1
/
8
5
1
/
2
x 19
1
/
8
5
1
/
2
x 24
1
/
8
5
1
/
2
x 33
5
/
8
5
1
/
2
x 42
1
/
8
5
1
/
2
x 61
1
/
8
5
1
/
2
x 61
1
/
8
(14 x 49)
(14 x 49)
(14 x 61)
(14 x 85)
(14 x 107)
(14 x 156)
(14 x 156)
Table I-GI-2. Low vertical fan-coil component data
unit size
03
04
06
Coil Data
Face Area — Ft
2
(cm
2
)
1.1 (1020)
1.6 (1490)
2.1 (1950)
LxDxH — In. (cm)
2-Row
20x1.7x8 (51x4x20)
29.5x1.7x8 (75x4x20)
38x1.7x8 (97x4x20)
3-Row
20x2.6x8 (51x7x20)
29.5x2.6x8 (75x7x20)
38x2.6x8 (97x7x20)
Volume — Gal. (Liters)
1-Row (Heat)
.08 (.30)
.11 (.42)
.14 (.53)
2-Row
.15 (.57)
.22 (.83)
.28 (1.06)
3-Row
.23 (.87)
.33 (1.25)
.42 (1.59)
Fins/Ft
2-Row
144 (4.7)
144 (4.7)
144 (4.7)
3-Row
144 (4.7)
144 (4.7)
144 (4.7)
Fan/Motor Data
Fan Quantity
1
1
1
Size — Dia”x Width” (cm)
5x23 (13x59)
5x32 (13x83)
5x41 (13x105)
Motor Quantity
1
1
1
Filter Data
1” (2.5 cm) TA
Quantity
1
1
1
Size — In. (cm)
8
7
/
8
x24
1
/
8
(23x61)
8
7
/
8
x33
5
/
8
(23x85)
8
7
/
8
x 42
1
/
8
(23x107)
Summary of Contents for UniTrane FC
Page 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...
Page 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...
Page 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...
Page 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...
Page 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...
Page 77: ......
Page 78: ......
Page 79: ......