UNT-SVX07A-EN
21
Installation
dimensions
& weights
Inverted Vertical Recessed, Model N
Inverted vertical recessed unit dimensions & weights, in-lbs.
unit
size
02-03
04
06
08
10-12
A
2’-3
7
/
8
”
2’-8
7
/
8
”
3’-6
3
/
8
”
4’-2
7
/
8
”
5’-9
7
/
8
”
B
1’-9
5
/
16
”
2’-2
5
/
16
”
2’-11
13
/
16
”
3’-8
5
/
16
”
5’-3
5
/
16
”
C
1’-10
13
/
16
”
2’-3
13
/
16
”
3’-1
5
/
16
”
3’-9
13
/
16
”
5’-4
13
/
16
”
D
2
3
/
8
”
2
3
/
8
”
2
3
/
8
”
4
1
/
8
”
4
1
/
8
”
E
3’-11”
4’-3”
5’-3”
5’-5
1
/
2
”
7’-5
1
/
2
”
F
2’-6”
2’-6”
2’-6”
2’-9
1
/
2
”
2’-9
1
/
2
”
G
2’-2
1
/
2
”
2’-2
1
/
2
”
2’-2
1
/
2
”
2’-3
1
/
2
”
2’-3
1
/
2
”
H
3’-6”
4’-0”
4’-9”
5’-3”
7’-3”
operating weight
78
88
128
139
253
shipping weight
68
78
118
129
243
Notes:
1. Coil connections are always on the side opposite the control box.
2. Coil connections are
5
/
8
” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
Dimension 'D' refers to the required
minimum distance between the finished
floor, and the bottom of the unit.
Summary of Contents for UniTrane FC
Page 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...
Page 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...
Page 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...
Page 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...
Page 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...
Page 77: ......
Page 78: ......
Page 79: ......