UNT-SVX07A-EN

59

Operation

sequence of
operation

Zone Sensor
The Tracer

 

ZN520 controller accepts the

following zone sensor module inputs:
• Space temperature measurement

(10k

 thermistor)

• Local setpoint (either internal or

external on the zone sensor module)

• Fan switch
• Timed override (On) and Cancel timed

override

• Communication jack

Space Temperature Measurement
Trane zone sensors use a 10kW
thermistor to measure the space
temperature. Typically, zone sensors are
wall-mounted in the room and include a
space temperature thermistor. As an
option, the zone sensor can be unit-
mounted with a separate space
temperature thermistor located in the
unit’s return air stream. If both a
hardwired and communicated space
temperature value exist, the controller
ignores the hardwired space
temperature input and uses the
communicated value.

External Setpoint Adjustment
Zone sensors with an external setpoint
adjustment (1k

) provide the Tracer

ZN520 controller with a local setpoint (50
to 85°F or 10 to 29.4°C). The external
setpoint is exposed on the zone sensor’s
front cover.

When the hardwired setpoint adjustment
is used to determine the setpoints, all unit
setpoints are calculated based on the
hardwired setpoint value, the configured
setpoints, and the active mode of the
controller. The hardwired setpoint is used
with the controller’s occupancy mode
(occupied, occupied standby, or unoccu-
pied), the heating or cooling mode, the
temperature deadband values, and the
heating and cooling setpoints (high and
low limits) to determine the controller’s
active setpoint.

When a building automation system or
other controller communicates a setpoint
to the controller, the controller ignores
the hardwired setpoint input and uses
the communicated value. The exception
is the unoccupied mode, when the
controller always uses the stored default
unoccupied setpoints. After the controller
completes all setpoint calculations, based
on the requested setpoint, the occupancy

mode, the heating and cooling mode, and
other factors, the calculated setpoint is
validated against the following setpoint
limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit

These setpoint limits only apply to the
occupied and occupied standby heating
and cooling setpoints. These setpoint
limits do not apply to the unoccupied
heating and cooling setpoints stored in
the controller’s configuration.

When the controller is in unoccupied
mode, it always uses the stored unoccu-
pied heating and cooling setpoints.The
unit can also be configured to enable or
disable the local (hardwired) setpoint.
This parameter provides additional
flexibility to allow you to apply communi-
cated, hardwired, or default setpoints
without making physical changes to the
unit.

Similar to hardwired setpoints, the
effective setpoint value for a communi-
cated setpoint is determined based on
the stored default setpoints (which
determines the occupied and occupied
standby temperature deadbands) and
the controller’s occupancy mode.

Fan Switch
The zone sensor fan switch provides the
controller with an occupied (and occupied
standby) fan request signal (Off, Low,
Medium, High, Auto). If the fan control
request is communicated to the
controller, the controller ignores the
hardwired fan switch input and uses the
communicated value. The zone sensor
fan switch input can be enabled or
disabled through configuration using the
Rover service tool. If the zone sensor
switch is disabled, the controller resorts
to its stored configuration default fan
speeds for heating and cooling, unless the
controller receives a communicated fan
input.

When the fan switch is in the off position,
the controller does not control any unit
capacity. The unit remains powered and
all outputs drive to the closed position.
Upon a loss of signal on the fan speed
input, the controller reports a diagnostic
and reverts to using the default fan
speed.

On/Cancel Buttons
Momentarily pressing the on button
during unoccupied mode places the
controller in occupied bypass mode for
120 minutes. You can adjust the number
of minutes in the unit controller
configuration using Rover service tool.
The controller remains in occupied
bypass mode until the override time
expires or until you press the Cancel
button.

Communication jack
Use the RJ-11 communication as the
connection point from Rover™ service
tool to the communication link — when
the communication jack is wired to the
communication link at the controller. By
accessing the communication jack via
Rover™, you can access any controller
on the link.

Communications
Tracer

 

ZN520 controller communicates

via Trane’s LonTalk protocol. Typically, a
communication link is applied between
unit controllers and a building automation
system. Communication also is possible
via Rover, Trane’s service tool. Peer-to-
peer communication across controllers is
possible even when a building
automation system is not present. You do
not need to observe polarity for LonTalk
communication links.

The controller provides six 0.25-inch
quick-connect terminals for the LonTalk
communication link connections, as
follows:
• Two terminals for communication to the

board

• Two terminals for communication from

the board to the next unit (daisy chain)

• Two terminals for a connection from the

zone sensor back to the controller

Table O-SO-16.  Zone sensor wiring
connections

TB1

description

1

space temperature

2

common

3

setpoint

4

fan mode

5

communications

6

communications

Summary of Contents for UniTrane FC

Page 1: ...Installation Operation andMaintenance UniTrane Fan Coil Force Flo Air Conditioners 200 to 1 200 cfm Models FC FF ZO and later design sequence Low vertical models FCKB FCLB SO and later design sequenc...

Page 2: ...ote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency drive...

Page 3: ...X04A EN UniTrane Fan Coil Catalog UNT PRC001 EN Force Flo Cabinet Heater Catalog CAB PRC001 EN Installation 2 general information 2 dimensions weights 10 pre installation considerations 28 mechanical...

Page 4: ...Q drain pan tocollectcondensate Factory installed andtestedcontrols Damperallowsup to 100 fresh air switch option can be ordered with a low voltage 24 volts AC transformer and three fan speed relays T...

Page 5: ...uctcollar B frontbargrille C frontstampedlouver D frontquadgrille G topquadgrille H topbargrille J topductcollar Digit 15 color 0 nopaint concealedunitsonly 1 deluxebeige 4 driftwoodgrey 2 softdove 5...

Page 6: ...mtdfansp w setpnt X unitmtdfansp w wallmtdsetpnt Y unitmtd fansp wallmtdsetpntw comm Z unitmtdfansp on cancel setpnt w comm 1 wallmtd on cancelw comm 2 wall mtd fan speed setpnt on cancel w comm 3 uni...

Page 7: ...x15 145x4x15 Volume Gal Liters 12 45 12 45 15 57 22 83 28 1 06 42 1 59 42 1 59 Fins Ft cm 48 1 6 48 1 6 48 1 6 48 1 6 48 1 6 48 1 6 48 1 6 Fan MotorData FanQuantity 1 1 1 2 2 3 3 Size Dia x Width cm 6...

Page 8: ...odel C horizontal concealed model D horizontal cabinet model E horizontal recessed model F wall hung cabinet model L low vertical concealed model K low vertical cabinet model J slope top cabinet model...

Page 9: ...tallation general information Factory Installed Piping Packages Note This figure shows piping package components and basic arrangement It is not an accurate pictorial of what factory installed piping...

Page 10: ...6 5 4 13 16 D 1 5 5 16 1 10 5 16 2 7 13 16 3 4 5 16 4 11 5 16 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 operating weight 81 109 139 147 200 shippingweight 68 96 123 131 182 Notes 1 Coil connecti...

Page 11: ...6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 3 5 5 16 3 10 5 16 4 7 3 16 5 4 5 16 6 11 5 16 operatingweight 97 125 155 164 218 shippingweight 84 112 139 148 200 Notes 1 Coil connections are...

Page 12: ...2 0 3 8 2 9 7 8 3 6 3 8 5 1 3 8 E 1 6 1 8 1 11 1 8 2 8 5 8 3 5 1 8 5 0 1 8 F 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 operatingweight 81 109 139 147 200 shippingweight 68 96 123 131 182 Notes 1 C...

Page 13: ...4 F 3 5 5 16 3 10 5 16 4 7 3 16 5 4 5 16 6 11 5 16 G 8 5 8 8 1 8 9 7 8 8 1 8 8 5 8 H 1 4 1 10 2 4 3 4 4 10 J 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 operatingweight 97 125 155 164 218 shippingweigh...

Page 14: ...1 8 2 8 5 8 3 5 1 8 5 0 1 8 F 2 8 7 16 3 1 7 16 3 10 15 16 4 7 7 16 6 2 7 16 G 2 10 5 16 3 3 5 16 4 0 13 16 4 9 5 16 6 4 5 16 H 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 operatingweight 78 88 128 139...

Page 15: ...1 6 2 0 2 6 3 6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 operatingweight 97 125 155 164 218 shipping weight 84 112 139 148 200 Notes 1 Coil conne...

Page 16: ...2 2 9 1 2 G 2 3 8 2 3 8 2 3 8 4 1 8 4 1 8 H 3 6 4 0 4 9 5 3 7 3 J 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 2 2 3 1 2 operatingweight 78 88 128 139 253 shipping weight 68 78 118 129 243 Notes 1 Coil connections a...

Page 17: ...1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 3 5 5 16 3 10 5 16 4 7 13 16 5 4 5 16 6 11 5 16 operatingweight 97 125 155 164 218 shipping weight 84 112 139 148 200...

Page 18: ...6 3 9 15 16 D 1 10 5 16 2 7 13 16 3 4 5 16 E 2 0 1 4 2 9 3 4 3 6 1 4 operatingweight 109 139 147 shipping weight 96 123 131 Notes 1 Coil connections are always on the drain pan side and opposite the c...

Page 19: ...1 1 5 16 11 7 16 D 2 0 2 6 3 6 E 2 0 1 4 2 9 3 4 3 6 1 4 operatingweight 125 155 164 shipping weight 112 139 148 Notes 1 Coil connections are always on the drain pan side and opposite the control box...

Page 20: ...8 7 1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 2 0 2 9 1 2 3 6 5 1 F 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 G 8 5 8 8 1 8 9 7 8 8 1 8 8 5 8 H 1 4 1 10 2 4 3 4 4 10 operatingweight 97 125 155 164 218 sh...

Page 21: ...3 11 4 3 5 3 5 5 1 2 7 5 1 2 F 2 6 2 6 2 6 2 9 1 2 2 9 1 2 G 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 2 2 3 1 2 H 3 6 4 0 4 9 5 3 7 3 operatingweight 78 88 128 139 253 shipping weight 68 78 118 129 243 Notes 1 C...

Page 22: ...22 UNT SVX07A EN Fan Coil Coil Connections Vertical Units Fan Coil Coil Connections Horizontal Units Installation dimensions weights...

Page 23: ...7A EN 23 Installation dimensions weights Force Flo Coil Connections Vertical Units Force Flo Coil Connections Horizontal Units HR Hot Water Return HS Hot Water Supply Force Flo Coil Connections Invert...

Page 24: ...mensions weights Fresh Air Opening Locations Horizontal Units Models C D and E Fresh Air Opening Dimensions Horizontal Units Unit Size 02 03 04 06 08 10 12 A 1 6 1 11 2 8 1 2 3 5 5 0 B 1 9 5 16 2 2 5...

Page 25: ...nsions weights Fresh Air Opening Locations Vertical Units Models A B F J Fresh Air Opening Dimensions Vertical Units Unit Size 02 03 04 06 08 10 12 A 1 6 1 11 2 8 1 2 3 5 5 0 B 1 9 5 16 2 2 5 16 2 11...

Page 26: ...3 8 x 4 3 4 1 04 24 3 8 x 7 1 2 1 06 33 1 8 x 7 1 2 2 08 37 1 2 x 7 1 2 3 10 12 58 1 4 x 7 1 2 4 CLEARANCE FOR DRAINAGE CONTINUOUS MORTAR RIBS TOP AND BOTTOM WOVENALUMINUM INSECTSCREEN 1 8 1 8 1 2 1...

Page 27: ...5 1 2 6 D 1 1 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 4 5 8 5 1 8 E 8 5 8 8 1 8 7 5 8 7 1 8 6 5 8 6 1 8 5 5 8 5 1 8 4 5 8 Projection Panel Dimensions Unit Size 02 03 04 06 08 10 12 A 3 11 4 3 5 3 5 5 1...

Page 28: ...al of the damage immediately by phone and mail Request an immediate joint inspection of the damage by the carrier and consignee Notify your Trane representative of the damage and arrange for repair Ha...

Page 29: ...te the following checklist before beginning unit installation Verify the unit size and tagging with the unit nameplate Make certain the floor or foundation is level solid and sufficient to support the...

Page 30: ...rns and transitions avoid sharp turns and use proportional splits turning vanes and air scoops when necessary 3 When possible construct and orient supply ductwork turns in the same direction as the fa...

Page 31: ...essary by punching out the overflow drain nipple on the auxiliary drain pan Next place a 3 8 inch inside diameter flexible plastic tube over the nipple and secure with a field supplied hose clamp Note...

Page 32: ...package the switch and coiled lead wires ship inside the piping side end panel The installer should position the lockout switch on the supply water line of the unit by sliding its spring connector ov...

Page 33: ...ropriate valve curve shown in Chart I MR 1 on page 34 to determine which setting is necessary to achieve the appropriate pressure drop The M line is the appropriate line 3 Carefully remove the Schrade...

Page 34: ...tallation Note Instructions for using this chart are on the previous page For the manual circuit setter provided with the fan coil or Force Flo use the M line for reference Chart I MR 1 Manual circuit...

Page 35: ...require one psig of pressure at the steam trap discharge for each two feet elevation to ensure continuous condensate removal 8 Proper steam trap selection and installation is necessary for satisfactor...

Page 36: ...oes not have a disconnect switch the power leads and capped ground wire are inside the control panel If the unit has a disconnect switch the power leads are wired to the junction box switch on the con...

Page 37: ...04 0 6 06 04 0 5 06 04 1080 800 600 06 1 4 12 09 0 9 12 09 0 6 12 09 1080 800 600 08 1 7 13 10 1 0 13 10 0 8 13 10 1080 800 600 10 1 0 06 04 0 6 06 04 0 5 06 04 1080 800 600 1 4 12 09 0 9 12 09 0 6 1...

Page 38: ...low vertical fan coils unit size unitvoltage kW kW kW kW 03 115 1 0 1 5 2 0 04 115 1 0 1 5 2 0 2 5 06 115 1 0 1 5 2 0 2 5 Low vertical units are only available with electric heat in combination with t...

Page 39: ...8 7 5 31 3 277 60 1 2 3 0 10 9 4 5 16 3 7 5 27 1 208 60 3 3 2 25 6 3 3 3 9 2 5 7 15 9 240 60 3 3 3 0 7 3 4 5 10 9 7 5 18 1 480 60 3 4 3 0 3 7 4 5 5 5 7 5 9 1 12 208 60 1 2 2 25 10 9 3 3 15 9 6 6 31 8...

Page 40: ...9 240 3 3 2 5 7 5 18 1 480 3 4 2 5 7 5 9 1 208 1 2 3 4 7 9 38 0 240 1 2 4 5 10 5 43 8 06 277 60 1 2 4 5 10 5 38 0 208 3 3 3 4 7 9 21 9 240 3 3 4 5 10 5 25 3 480 3 4 4 5 10 5 12 7 208 1 2 4 5 10 1 48...

Page 41: ...startup Failure to have panels and filters in place may cause motor overload Horizontal Units Install horizontal units suspended from the ceiling using the four 5 8 inch diameter double key slot hang...

Page 42: ...alla tion position and use 2 or 3 5 inch bolts whichever is best suited for installation Also install two safety chains assemblies on these sizes Note Expansion collar is furnished with fan coil with...

Page 43: ...omm jack Figure I IP 3 Zone sensor with on cancel and comm jack Figure I IP 2 Zone sensor with off auto high low fan speeds setpoint knob on cancel and comm jack Figure I IP 5 Zone sensor only install...

Page 44: ...a 2 x 4 electrical junction box Follow the instructions given in the Interconnection Wiring section and route the wires as shown in the wiring diagram Refer to the typical wiring diagram or to the uni...

Page 45: ...units meets the national Fire Protection Association N F P A Standard 90A or 90B concerning the use of concealed ceiling spaces as return air plenums Verify correct ceiling opening dimensions on unit...

Page 46: ...using 277VAC Do not use a trunk and branch configuration if possible Trunk and branch configurations shorten the distance cable can be run Communication Wiring Units with Tracer ZN510 and ZN520 Only...

Page 47: ...dling section Check nameplate unit data so that it matches the sales order requirements pre startup requirements Unit Location 1 Ensure the unit location is adequate for unit dimensions ductwork pipin...

Page 48: ...h option 2 Position the fan mode switch to either high medium low or the auto position 3 Rotate the setpoint dial on the zone startup Installation sensor module to 55 F for cooling or 85 F for heating...

Page 49: ...be broken if field modifications are needed However switches must be properly set for the unit to operate safely and properly See Figure O GI 1 Manual Fan Mode Switch The manual fan mode switch is av...

Page 50: ...cycles to maintain setpoint temperature Fresh air damper option is open Operation sequence of operation Tracer ZN520 Operation Off Fan is off control valve options and fresh air damper options close T...

Page 51: ...main coil hot water assumed in aux coil Binary Inputs BIP1 Low Temperature Detection Option The factory hard wires the low temperature detection sensor to binary input 1 BIP1 on the Tracer ZN010 and Z...

Page 52: ...rs include a thermistor soldered to the sensor s circuit board Unit mounted sensors include a return air sensor in the unit s return air stream 3 Changeover units include an entering water temperature...

Page 53: ...damper position goes to the economizer standby mini mum position The economizer standby minimum position can be changed using Rover service tool In the occupied standby mode the controller uses the oc...

Page 54: ...discharge air temperature to its low limit Discharge Air Tempering The discharge air tempering function enables when cold outdoor air is brought in through the outdoor air damper causing the discharg...

Page 55: ...default determined by heat cool mode Continuous Fan Operation During occupied and occupied standby modes the fan normally is on For multiple speed fan applications the fan normally operates at the se...

Page 56: ...before initializing another sampling If the controller determines the entering water temperature is valid for heating or cooling it resumes normal heating cooling control and effectively disables ente...

Page 57: ...tic will not be generated when the controller commands the fan off A diagnostic will only be generated if the fan status input does not close after one minute from energizing a fan output or any time...

Page 58: ...include a return air sensor in the units return air stream 3 Changeover units include an entering water temperature sensor Table O SO 15 Analog inputs description terminals function range zone TB3 1...

Page 59: ...ovides additional flexibility to allow you to apply communi cated hardwired or default setpoints without making physical changes to the unit Similar to hardwired setpoints the effective setpoint value...

Page 60: ...ed Fresh air damper Enabled electric heat Enabled Baseboard heat Enabled Local fan mode failure On Valves Enabled Fresh air damper Enabled Electric Heat Enabled Baseboard heat Enabled Local setpoint f...

Page 61: ...ler 4 Through Rover Trane s service tool 5 Tracer ZN520 by using any other communicating device ab le to access the controller s diagnostic reset input 6 Tracer ZN520 by cycling the fan switch from Of...

Page 62: ...communicated to the controller the unitcontrols the fan to off The unit is not capable of heating or cooling when the controller is in this mode Valve override The controller can communicate a valve o...

Page 63: ...However based on thecurrent step in the test sequence the fresh air damper may not be open Refer to the Manual Output Test section Unit configuration The controller must be properly configured based...

Page 64: ...nit control options Figure M T 2 shows a relay board detail Additional information on switch settings follows Switch SW1 Controller Type SW1 determines the unit control type Position 1 indicates one o...

Page 65: ...he controller is in Manual output test mode If the LED blinks twice the controller is in Manual output test mode with one or more diagnostics present indicates whether the controller is powered on 24...

Page 66: ...ttempts to clear all diagnostics 2 For all 1 heat 1 cool applications including 2 pipe changeover BOP4 energizes in the cooling test stage and BOP5 energizes in the heat test stage This occurs even th...

Page 67: ...esh air opening they require an additional filter for the fresh air opening CAUTION Replace all panels and filters properly All unit panels and filters must be in place prior to unit startup Failure t...

Page 68: ...ed by operating experience Cleaning frequently is dependent upon system operating hours filter maintenance and efficiency and dirt load Follow the suggested methods in the following paragraphs Steam a...

Page 69: ...rt the fanboard when removing it from the unit Failure to properly support fanboard may result in minor to moderate personal injury Replacing the Motor The capacitor for all unit motors can be replace...

Page 70: ...by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that all capacitors have discharge...

Page 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...

Page 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...

Page 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...

Page 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...

Page 75: ...UNT SVX07A EN 75 typical wiring diagram Maintenance Tracer ZN510 with main and auxilliary valves...

Page 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...