Service and Maintenance
RT-SVX24J-EN
187
different times of the year.The sump water clarity should
be checked periodically.
The evaporative condenser has several design features to
reduce the possibility of biological growth in the sump.
These features include:
•
air inlets constructed to eliminate direct sunlight in the
sump
•
The sump flush sequence replenishes the sump with
fresh water 1 to 12 times per day depending on the
flush setting
•
The copper tubing in the coils is a natural biocide
Important:
Do not use chlorine tablets directly on
stainless steel surface as it can adversely
affect its corrosion resistance.
Always consult local codes for water treatment and waste
water removal requirements. Consult a water treatment
expert for water analysis and chemical treatment methods
and recommendations for specific applications.
If deemed necessary after consultation with local water
experts, there are various means of water treatment
available which can be field installed.
Microchannel Condenser Coil Repair and
Replacement
If microchannel condenser coil repair or replacement is
required, seek HVAC Knowledge Center information or
Service Guide document RT-SVB83*-EN for further details.