Unit Startup
128
RT-SVX24J-EN
Nom
Tons
CFM
Standard Filter Section (Pre Evap)
Final Filter Section (Post Evap)
Std 2"
High Eff
Throw
Away
Filters
90-95%
Low PD
Cartridg
e Filters
w/ 2"
Prefilter
90-95%
Low PD
Cartridg
e Filters
w/ 4"
Prefilter
90-95%
Cartridg
e Filters
w/ 2"
Prefilter
(c)
90-95%
Bag
Filters
w/ 2"
Prefilter
(c)
90-95%
Std Temp
Low PD
Cartridge
Filters
w/4”
Prefilter
(d)
90-95%
Std
Temp
Bag
Filters
w/ 2"
Prefilter
(e)
90-95%
Std Temp
Cartridg
e Filters
w/ 2"
Prefilter
(e)
90-95%
Hi Temp
Cartridge
Filters
w/ 2" Hi
Temp
Prefilter
(e)
90-95%
Hi Temp
HEPA w/
2" Hi
Temp
Prefilter
(f)
90-95%
Std
Temp
HEPA
Filters
w/ 2" Hi
Temp
Prefilter
(f)
150/162
23000
0.10
-
0.32
0.37
0.44
0.36
0.47
0.40
0.49
0.77
0.68
26000
0.14
-
0.43
0.47
0.54
0.48
0.58
0.52
0.64
0.97
0.85
30000
0.17
-
0.55
0.59
0.64
0.62
0.70
0.66
0.82
1.18
1.02
35000
0.21
-
0.69
0.73
0.76
0.78
0.83
0.82
1.02
1.40
1.20
40000
0.26
-
0.84
0.89
0.88
0.94
0.97
1.01
1.25
-
-
45000
0.30
-
1.00
1.07
1.02
1.13
1.12
1.22
1.51
-
-
50000
0.35
-
1.17
1.27
1.16
1.33
-
-
-
-
-
55000
0.41
-
1.36
-
-
1.55
-
-
-
-
-
58000
0.44
-
1.48
-
-
-
-
-
-
-
-
(a) Actual Supply Fan CFM Range:90/100 Ton 16,000-40,000;
105/118 Ton 19,000-45,000; 120/128 Ton 21,000-54,000; 130-162 Ton 23,000-58,000
(b) There is no pressure drop with Electric Heat DF configuration
(c) 120-162 Ton Max CFM 50,000
(d) 130-162 Ton Max CFM 55,500
(e) 120-162 Ton Max CFM 46,250
(f) 90-162 Ton Max CFM 37,000
Table 40. Component static pressure drops (
in. H
2
O) (continued)