Unit Startup
112
RT-SVX24J-EN
Table 38. Service test guide for component operation — part II of II
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Sump Pump
Sump Heater
Econo
Damper
Exhaust
Damper
VFD
Output
COMPRESSOR
90 - 105 Ton
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B
Closed
Closed
0%
Default
OFF
OFF
120 - 162 Ton
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B
Closed
Closed
0%
Default
OFF
OFF
CONDENSER FANS
90 - 105 Ton — Air Cooled
1A
Closed
Closed
0%
Default
OFF
OFF
1B & 1C
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B & 2C
Closed
Closed
0%
Default
OFF
OFF
120 - 150 Ton — Air Cooled
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
1C & 1D
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B & 2C
Closed
Closed
0%
Default
OFF
OFF
2D
Closed
Closed
0%
Default
OFF
OFF
100, 118, 128, 140, 162 Ton — Evaporative Cooled
1A
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
SUPPLY FAN
Closed
Closed
100%
Unocc
OFF
OFF
RETURN FAN
Closed
Closed
100%
Default
OFF
OFF
EXHAUST FAN
Closed
Closed
100%
Default
OFF
OFF
GAS HEAT
(Full Capacity)
Closed
Closed
100%
Unocc
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
Full Modulating
Closed
Closed
100%
Unocc
OFF
OFF
ELECTRIC HEAT
Closed
Closed
100%
Unocc
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
Stage 3
Closed
Closed
100%
Unocc
OFF
OFF
HYDRONIC HEAT
Closed
Closed
100%
Default
OFF
OFF
OUTSIDE AIR
DAMPERS
Closed
Closed
100%
Default
OFF
OFF
EXHAUST DAMPERS
Closed
Closed
100%
Default
OFF
OFF
EVAP COND
Sump Pump
Closed
Closed
100%
Default
ON
OFF
Sump Heater
Closed
Closed
100%
Default
OFF
ON