28
RTAA-SVX01A-EN
Installation — Mechanical
CAUTION
Evaporator Damage!
To prevent evaporator damage, do not exceed 215 psig (14.6 bar)
evaporator water pressure.
Evaporator Drain
A 3/4” drain connection is located under the outlet end of the evaporator. This
may be connected to a suitable drain to permit evaporator drainage during
unit servicing. A shutoff valve must be installed on the drain line.
Chilled Water Flow Switch
Chilled water flow protection is provided by the UCM without the need for a
chilled water flow switch. A flow switch for chilled water is strictly discre-
tionary but if not installed, a signal must be sent to the chiller to indicate that
water flow has been established, eg. chilled water pump motor starter
auxiliary contacts, building automation system, etc.
If additional chilled water flow protection is desired, use a field-installed flow
switch or differential pressure switch with the pump motor starter auxiliary
contacts to sense system water flow. Install and wire the flow switch in
series with the chilled water pump motor starter auxiliaries (refer to
“Interlock Wiring”).
Specific connection and schematic wiring diagrams are shipped with the unit.
Some piping and control schemes, particularly those using a single water
pump for both chilled and hot water, must be analyzed to determine how and
or if a flow sensing device will provide desired operation.
Follow the manufacturer's recommendations for selection and installation
procedures. General guidelines for flow switch installation are outlined below:
1.
Mount the switch upright, with a minimum of 5 pipe diameters of straight
horizontal run on each side. Do not install close to elbows, orifices or
valves.
NOTE:
The arrow on the switch must point in the direction of flow.
2.
To prevent switch fluttering, remove all air from the water system.
NOTE:
The UCM provides a 6-second time delay after a “loss-of flow”
diagnostic before shutting the unit down. Contact a qualified service
representative if nuisance machine shutdowns persist.
3.
Adjust the switch to open when water flow falls below nominal. Evapora-
tor data is shown in
Figure 16
Refer to
Table 1
for minimum flow recom-
mendations. Flow switch contacts are closed on proof of water flow.
4.
Install a pipe strainer in the entering evaporator water line to protect
components from water-borne debr‘is.
Summary of Contents for RTAA-100
Page 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Page 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Page 144: ...144 RTAA SVX01A EN Pump Package...
Page 146: ...146 RTAA SVX01A EN 3327...
Page 147: ...RTAA SVX01A EN 147...
Page 148: ...148 RTAA SVX01A EN 3328...
Page 149: ...RTAA SVX01A EN 149...
Page 150: ...150 RTAA SVX01A EN 6516...
Page 151: ...RTAA SVX01A EN 151...
Page 152: ...152 RTAA SVX01A EN 3329...
Page 153: ...RTAA SVX01A EN 153...
Page 154: ...154 RTAA SVX01A EN 6472...
Page 155: ...RTAA SVX01A EN 155...
Page 156: ...RTAA SVX01A EN 156 3330...
Page 157: ...157 RTAA SVX01A EN...
Page 158: ...158 RTAA SVX01A EN 6046...
Page 159: ...RTAA SVX01A EN 159...
Page 160: ...160 RTAA SVX01A EN 3331...
Page 161: ...RTAA SVX01A EN 161...
Page 162: ...162 RTAA SVX01A EN 6519...
Page 163: ...RTAA SVX01A EN 163...
Page 164: ...164 RTAA SVX01A EN 6047...
Page 165: ...RTAA SVX01A EN 165...
Page 166: ...166 RTAA SVX01A EN 3325...
Page 167: ...RTAA SVX01A EN 167...
Page 168: ...168 RTAA SVX01A EN 6048...
Page 169: ...RTAA SVX01A EN 169...
Page 172: ...172 RTAA SVX01A EN 3326...
Page 173: ...RTAA SVX01A EN 173...
Page 174: ...174 RTAA SVX01A EN 6049...
Page 175: ...RTAA SVX01A EN 175...
Page 176: ...176 RTAA SVX01A EN 6463...
Page 177: ......