RTAA-SVX01A-EN
101
Controls Interface
2-10 VDC/4-20 mA Input for External Chilled Water Setpoint (CWS) and
Current Limit Setpoint (CLS)
When either external CWS or external CLS is used on the optional Module
1U2, DIP switch SW1 positions 1 and/or 2 must be set to accommodate the
type of signal source the customer has chosen, either 2-10 VDC or 4-20 mA.
Position SW-1-1 sets 2-10 VDC/4-20 mA for external CWS. SW1-2 sets 2-10
VDC/4-20 mA for external CLS. The “OFF” setting configures the external
input for 2-10 VDC; the “ON” setting configures the external input for
4-20 mA.
Table 18
Compressor Overload DIP Switch Settings
Compressor
Tons
Volts/Hz
RLA
Primary Turns
Through Current
Transformer
Current
Transformer
Extension*
Overload Setting Dip
Sw/Decimal12345**
35
200/60
115
1
-02
01011/11
230/60
100
1
-01
11111/31
346/50
58
1
-10
01100/12
380/60
61
1
-10
10000/16
400/50
50
1
-10
00000/0
460/60
50
1
-10
00000/0
575/60
40
1
-09
01111/15
40
200/60
142
1
-02
11011/27
230/60
124
1
-02
10001/17
346/50
72
1
-01
00111/7
380/60
75
1
-01
01010/10
400/50
62
1
-10
10001/17
460/60
62
1
-10
10001/17
575/60
50
1
-10
00001/1
50
200/60
192
1
-03
11100/28
230/60
167
1
-03
10010/18
346/50
96
1
-01
11100/28
380/60
101
1
-02
00001/1
400/50
84
1
-01
10011/19
460/60
84
1
-01
10011/19
575/60
67
1
-10
10111/23
60
200/60
233
1
-04
10011/19
230/60
203
1
-04
01000/8
346/50
117
1
-02
01101/13
380/60
123
1
-02
10001/17
400/50
101
1
-02
00001/16
460/60
101
1
-02
00001/1
575/60
81
1
-01
10000/16
*The Current Transformer base part number is X1358025. The numbers in this column are suffixes to the base number.
**On the DIP switch, 1=ON, O=OFF The decimal value should be set in the compressor overload setting menu of the UCM. If the DIP
switch value does not match the decimal value entered into the UCM, the related compressor(s) will continue to run, but a
diagnostic will be initiated, both settings will be ignored, and the UCM will use the lowest possible trip setting value.
Summary of Contents for RTAA-100
Page 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Page 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Page 144: ...144 RTAA SVX01A EN Pump Package...
Page 146: ...146 RTAA SVX01A EN 3327...
Page 147: ...RTAA SVX01A EN 147...
Page 148: ...148 RTAA SVX01A EN 3328...
Page 149: ...RTAA SVX01A EN 149...
Page 150: ...150 RTAA SVX01A EN 6516...
Page 151: ...RTAA SVX01A EN 151...
Page 152: ...152 RTAA SVX01A EN 3329...
Page 153: ...RTAA SVX01A EN 153...
Page 154: ...154 RTAA SVX01A EN 6472...
Page 155: ...RTAA SVX01A EN 155...
Page 156: ...RTAA SVX01A EN 156 3330...
Page 157: ...157 RTAA SVX01A EN...
Page 158: ...158 RTAA SVX01A EN 6046...
Page 159: ...RTAA SVX01A EN 159...
Page 160: ...160 RTAA SVX01A EN 3331...
Page 161: ...RTAA SVX01A EN 161...
Page 162: ...162 RTAA SVX01A EN 6519...
Page 163: ...RTAA SVX01A EN 163...
Page 164: ...164 RTAA SVX01A EN 6047...
Page 165: ...RTAA SVX01A EN 165...
Page 166: ...166 RTAA SVX01A EN 3325...
Page 167: ...RTAA SVX01A EN 167...
Page 168: ...168 RTAA SVX01A EN 6048...
Page 169: ...RTAA SVX01A EN 169...
Page 172: ...172 RTAA SVX01A EN 3326...
Page 173: ...RTAA SVX01A EN 173...
Page 174: ...174 RTAA SVX01A EN 6049...
Page 175: ...RTAA SVX01A EN 175...
Page 176: ...176 RTAA SVX01A EN 6463...
Page 177: ......