96
RTAA-SVX01A-EN
Controls Interface
The equations for each type of reset are:
RETURN WATER TEMPERATURE RESET
CWS' = CWS + RESET RATIO
[START RESET - (TWE - TWL)]
and CWS' > or = CWS
and CWS' - CWS < or = MAXIMUM RESET
OUTDOOR AIR TEMPERATURE RESET
CWS' = CWS + RESET RATIO
[START RESET - TOD]
and CWS' > or = CWS
and CWS' - CWS < or = MAXIMUM RESET
CWS' is the new chilled water setpoint.
CWS is the active chilled water setpoint before any reset has occurred.
RESET RATIO is a user adjustable gain.
START RESET is a user adjustable reference.
TOD is the outdoor temperature.
TWE is the entering evaporator water temperature.
TWL is the leaving evaporator water temperature.
MAXIMUM RESET is a user adjustable limit, providing the maximum amount
of reset.
NOTE:
When any type of CWR is enabled, the UCM will step the CWS
toward the desired CWS' (based on the above equations and setup
parameters) at a rate of 1 F every 5 minutes. This applies when the chiller is
both running and off. Normally the chiller will start at the Differential-to-Start
value above a fully reset CWS or CWS'.
The values for RESET RATIO for each type of reset are:
Reset Type
Reset
Ratio Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
1O to 120%
1%
1%
50%
Outdoor
80 to -80%
1%
1%
10%
The values for START RESET for each type of reset are:
Reset Type
Start
Reset Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
4 TO 30 F
1 F
0.1C
10 F (5.6 C)
(2.2 to 16.7 C)
Outdoor
50 to 130 F
1 F
0.1 C
90 F (32.2 C)
(10 to 54.4 C
The values for MAXIMUM RESET for each type of reset are:
Reset
Type
Maximum
Reset Range
Increment
English Units
Increment
SI Units
Factory Default
Value
Return
1O to 20 F
1 F
0.1C
5 F (2.8 C)
(-17.8 to -6.7 C)
Outdoor
O to20 F
1 F
0.1 C
5 F (2.8 C)
(-17.8 to -6.7 C)
Summary of Contents for RTAA-100
Page 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Page 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Page 144: ...144 RTAA SVX01A EN Pump Package...
Page 146: ...146 RTAA SVX01A EN 3327...
Page 147: ...RTAA SVX01A EN 147...
Page 148: ...148 RTAA SVX01A EN 3328...
Page 149: ...RTAA SVX01A EN 149...
Page 150: ...150 RTAA SVX01A EN 6516...
Page 151: ...RTAA SVX01A EN 151...
Page 152: ...152 RTAA SVX01A EN 3329...
Page 153: ...RTAA SVX01A EN 153...
Page 154: ...154 RTAA SVX01A EN 6472...
Page 155: ...RTAA SVX01A EN 155...
Page 156: ...RTAA SVX01A EN 156 3330...
Page 157: ...157 RTAA SVX01A EN...
Page 158: ...158 RTAA SVX01A EN 6046...
Page 159: ...RTAA SVX01A EN 159...
Page 160: ...160 RTAA SVX01A EN 3331...
Page 161: ...RTAA SVX01A EN 161...
Page 162: ...162 RTAA SVX01A EN 6519...
Page 163: ...RTAA SVX01A EN 163...
Page 164: ...164 RTAA SVX01A EN 6047...
Page 165: ...RTAA SVX01A EN 165...
Page 166: ...166 RTAA SVX01A EN 3325...
Page 167: ...RTAA SVX01A EN 167...
Page 168: ...168 RTAA SVX01A EN 6048...
Page 169: ...RTAA SVX01A EN 169...
Page 172: ...172 RTAA SVX01A EN 3326...
Page 173: ...RTAA SVX01A EN 173...
Page 174: ...174 RTAA SVX01A EN 6049...
Page 175: ...RTAA SVX01A EN 175...
Page 176: ...176 RTAA SVX01A EN 6463...
Page 177: ......