Diagnostics
External Chilled Water Setpoint
IFW
a.
Not “Enabled”: no diagnostics.
b.
“Enabled”: Out-Of-Range Low, set diagnostic.
Out-Of-Range Hi, no diagnostic.
External Current Limit Setpoint
IFW
a.
Not “Enabled”: no diagnostics.
b.
“Enabled”: Out-Of -Range Low, set diagnostic.
Out-Of -Range Hi, no diagnostic.
EXV Elec. Drive CKT - Rfgt Ckt 1
CMR
Run the EXV electrical drive circuit test both on demand from
the human interface and just before either a circuit or one of a
pair of circuits starts.
EXV Elec. Drive CKT - Rfgt Ckt 2
CMR
Same as Diagnostic for Ckt 1, above.
High Diff. Press. - Ckt 1
CMR
The difference between the Condenser pressure and the
evaporator pressure exceeded 350 PSID for 0.8-5.0 seconds.
320 PSID must hold, 320 + to trip in One Hour.
High Diff. Press - Ckt 2
CMR
Same as Diagnostic for Ckt 1, above.
High Oil Temp - Cprsr A
CMR
Entering Oil Temp to given compressor exceeded 170F. Time to
trip is given by equation: trip time = (190-0il Temp) x 180 sec/F.
High Oil Temp - Cprsr B
CMR
Same as Cprsr A, above.
High Oil Temp - Cprsr C
CMR
Same as Cprsr A, above.
High Oil Temp - Cprsr D
CMR
Same as Cprsr A, above.
High Pressure Cutout - Cprsr A
CMR
A high pressure cutout was detected on Cprsr A; trip at 405 +
or -7 PSIG.
High Pressure Cutout - Cprsr B
CMR
A high pressure cutout was detected on Cprsr B; trip at 405 +
or -7 PSIG.
High Pressure Cutout - Cprsr C
CMR
A high pressure cutout was detected on Cprsr C; trip at 405 +
or -7 PSIG.
High Pressure Cutout - Cprsr D
CMR
A high pressure cutout was detected on Cprsr 0; trip at 405 +
or -7 PSIG.
Loss of Local Display Panel COM
IFW
The 1U1 has detected a loss of IPC communication with the
Local Display panel for at least 15 seconds.
Low Chilled Water Temp (Unit off)
IFW
The chilled water temp. fell below the cutout setpoint while the
compressors were not running.
Low Chilled Water Temp (Unit on)
MAR
The chilled water temp. fell below the cutout setpoint while the
compressors were running for 30 degree F Seconds.
Low Differential Press - Ckt 1
CMR
The fan control algorithm detected a low differential Temper-
ature/Pressure condition that existed for more than 180
contiguous seconds. Trip point is 40 PSID.
Low Differential Press - Ckt 2
CMR
Same as Diagnostic for Ckt 1, above.
Low Evap Rfgt Temp - Ckt 1
CMR
a.
The Saturated Evap Rfgt Temp - Circuit 1 dropped below
the Low Rfgt Temp Cutout Setpoint while the circuit was
running for 30 deg F seconds.
b.
See the low ambient ignore time on startup.
Low Evap Rfgt Temp - Ckt 2
CMR
Same as Diagnostic for Ckt 1, above.
Table 19
Diagnostic Codes
Diagnostic Description
Type
Cause
Summary of Contents for RTAA-100
Page 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Page 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Page 144: ...144 RTAA SVX01A EN Pump Package...
Page 146: ...146 RTAA SVX01A EN 3327...
Page 147: ...RTAA SVX01A EN 147...
Page 148: ...148 RTAA SVX01A EN 3328...
Page 149: ...RTAA SVX01A EN 149...
Page 150: ...150 RTAA SVX01A EN 6516...
Page 151: ...RTAA SVX01A EN 151...
Page 152: ...152 RTAA SVX01A EN 3329...
Page 153: ...RTAA SVX01A EN 153...
Page 154: ...154 RTAA SVX01A EN 6472...
Page 155: ...RTAA SVX01A EN 155...
Page 156: ...RTAA SVX01A EN 156 3330...
Page 157: ...157 RTAA SVX01A EN...
Page 158: ...158 RTAA SVX01A EN 6046...
Page 159: ...RTAA SVX01A EN 159...
Page 160: ...160 RTAA SVX01A EN 3331...
Page 161: ...RTAA SVX01A EN 161...
Page 162: ...162 RTAA SVX01A EN 6519...
Page 163: ...RTAA SVX01A EN 163...
Page 164: ...164 RTAA SVX01A EN 6047...
Page 165: ...RTAA SVX01A EN 165...
Page 166: ...166 RTAA SVX01A EN 3325...
Page 167: ...RTAA SVX01A EN 167...
Page 168: ...168 RTAA SVX01A EN 6048...
Page 169: ...RTAA SVX01A EN 169...
Page 172: ...172 RTAA SVX01A EN 3326...
Page 173: ...RTAA SVX01A EN 173...
Page 174: ...174 RTAA SVX01A EN 6049...
Page 175: ...RTAA SVX01A EN 175...
Page 176: ...176 RTAA SVX01A EN 6463...
Page 177: ......